Skip to main content
Schneider Electric LC1G2254EHEA

Schneider LC1G2254EHEA TeSys Giga Contactor, AC-3 225 A

MPNLC1G2254EHEA
Active

Schneider Electric TeSys Giga series, 4-pole contactor, LC1G2254EHEA, 225 A AC-3, control 48…130 V AC/DC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G2254EHEA key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage48...130 V AC 50/60 Hz 48...130 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min
Breaking capacity2050 A at 440 V
[Ie] rated operational current225 A (at 330 A (at <104 °F (40 °C)) at <= 1000 V AC-1
[Ith] conventional free air thermal current330 A (at 104 °F (40 °C))
Inrush power in190 W

All specifications

LC1G2254EHEA additional specifications
ParameterValue
Maximum horse power rating60 hp at 200/208 V 60 Hz 75 hp at 230/240 V 60 Hz 150 hp at 460/480 V 60 Hz 150 hp at 575/600 V 60 Hz
Power dissipation per pole20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A
Inrush power in VA (50/60 hz, AC)260 VA
Hold-in power consumption in5.0 W
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.4 in (35 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth7.6 in (193 mm)
Width5.6 in (143 mm)
Height10.04 in (255 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.00015 Ohm
Device short nameLC1G
Tightening torque159.3 lbf.in (18 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating250 A aM at 200 A aM at 400 A gG at 400 A UL Type J at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity2720 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

The LC1G2254EHEA: Coil accepts 48 to 130 V AC 50/60 Hz or DC, with built-in bidirectional peak limiting to suppress transients. Mechanical durability is 8 million cycles, and power dissipation sits at 8 W per pole in AC-3 at 225 A. Power circuit connections accept bar (25×6 mm busbar) or ring lugs up to 185 mm²; control circuit uses push-in terminals for 0.2…2.5 mm² solid or stranded wire.

Mounts on a plate with a 35 mm pitch between poles. Front face with shrouds gives IP2X protection. Overvoltage category III. Auxiliary contacts: 1 NO + 1 NC built-in. Safety reliability: B10d = 400,000 cycles at nominal load per EN/ISO 13849-1. Available through preferred supplier catalogs under the TeSys Giga line; keep this order code on the BOM to avoid maverick spend on alternate SKUs.

Frequently asked questions

What is the control voltage range for LC1G2254EHEA?

The control voltage is 48 to 130 V AC 50/60 Hz and 48 to 130 V DC.

What standards does this contactor comply with?

It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40 Annex JJ.

What is the rated making capacity at 440 V?

The rated making capacity is 2720 A at 440 V.

MPN
LC1G2254EHEA