Skip to main content

Schneider Electric LC1G Series

22 variants · Schneider Electric

About the Schneider Electric LC1G Series

AO Ctrl is a China industrial automation distributor and independent sourcing agent for Schneider Electric LC1G Series components — the parts repair and maintenance teams source here when a machine is down or the line is no longer sold locally — with the physical condition of every unit stated up front. The Schneider Electric LC1G Series series groups 22 related part numbers, each listed with full specifications, a datasheet where available, and an RFQ option. Every variant in the range shares a common color of Dark grey, depth of 7.6 in (193 mm) and insulation voltage ui of 1000 V. Variants differ by application, breaking capacity and coil voltage, so you can match the exact application your application requires using the selection guide below. The range mixes active and legacy part numbers, so you can source both current Schneider Electric LC1G Series variants and discontinued ones from a single page.

Select a variant by

Application
Power switching · Power switching Motor control
Breaking capacity
1040 A at 440 V · 1280 A at 440 V
Coil voltage
24...48 V AC 50/60 Hz 24...48 V DC · 48...130 V AC 50/60 Hz 48...130 V DC · 100...250 V AC 50/60 Hz 100...250 V DC · 200...500 V AC 50/60 Hz 200...500 V DC
Current
115 A (at 250 A (at <104 °F (40 °C)) at <= 1000 V AC-1 · 150 A (at 275 A (at <104 °F (40 °C)) at <= 1000 V AC-1 · 250 A (at 115 A (at <140 °F (60 °C)) at <= 440 V AC-3 · 275 A (at 150 A (at <140 °F (60 °C)) at <= 440 V AC-3
Height
7.6 in (193 mm) · 10.04 in (255 mm)
Utilization category
AC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8 a AC-8b DC-1 DC-3 DC-5 · AC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8b AC-8 a DC-1 DC-3 DC-5 · AC-3 AC-3e AC-1 AC-5 a AC-5b AC-6 a AC-6b DC-1 DC-3 DC-5
Width
4.3 in (108 mm) · 5.6 in (143 mm)

Shared specifications

Color
Dark grey
Depth
7.6 in (193 mm)
Insulation voltage ui
1000 V
Main product or component type
Contactor
Mechanical life cycles
8 Mcycles
Operating temperature
-13...140 °F (-25...60 °C)
Operating time
40...70 ms closing 15...50 ms opening
Permissible ambient air temperature around the device
-40...158 °F (-40...70 °C) at Uc
Storage temperature
-76...176 °F (-60...80 °C)
Temp operating max
60 °C
Temp operating min
-25 °C
Temp storage max
80 °C

Variant comparison

ParameterLC1G150EHENLC1G115EHEALC1G115KUENLC1G115LSEALC1G1154BEEALC1G1154EHEA
ApplicationPower switching Motor controlPower switching Motor controlPower switching Motor controlPower switching Motor controlPower switchingPower switching
Breaking capacity1280 A at 440 V1040 A at 440 V1040 A at 440 V1040 A at 440 V1040 A at 440 V1040 A at 440 V
Coil voltage48...130 V AC 50/60 Hz 48...130 V DC48...130 V AC 50/60 Hz 48...130 V DC100...250 V AC 50/60 Hz 100...250 V DC200...500 V AC 50/60 Hz 200...500 V DC24...48 V AC 50/60 Hz 24...48 V DC48...130 V AC 50/60 Hz 48...130 V DC
Current275 A (at 150 A (at <140 °F (60 °C)) at <= 440 V AC-3250 A (at 115 A (at <140 °F (60 °C)) at <= 440 V AC-3250 A (at 115 A (at <140 °F (60 °C)) at <= 440 V AC-3250 A (at 115 A (at <140 °F (60 °C)) at <= 440 V AC-3115 A (at 250 A (at <104 °F (40 °C)) at <= 1000 V AC-1115 A (at 250 A (at <104 °F (40 °C)) at <= 1000 V AC-1
Height7.6 in (193 mm)10.04 in (255 mm)7.6 in (193 mm)10.04 in (255 mm)10.04 in (255 mm)10.04 in (255 mm)
Utilization categoryAC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8b AC-8 a DC-1 DC-3 DC-5AC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8b AC-8 a DC-1 DC-3 DC-5AC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8 a AC-8b DC-1 DC-3 DC-5AC-1 AC-3 AC-3e AC-4 AC-5 a AC-5b AC-6 a AC-6b AC-8b AC-8 a DC-1 DC-3 DC-5AC-3 AC-3e AC-1 AC-5 a AC-5b AC-6 a AC-6b DC-1 DC-3 DC-5AC-3 AC-3e AC-1 AC-5 a AC-5b AC-6 a AC-6b DC-1 DC-3 DC-5
Width4.3 in (108 mm)4.3 in (108 mm)4.3 in (108 mm)4.3 in (108 mm)5.6 in (143 mm)5.6 in (143 mm)

Request a quote on any Schneider Electric LC1G Series part number and we confirm price, availability and lead time per line — including end-of-life, allocation-constrained, and machine-down urgent requirements.

All variants