Control voltage and coil technology
Utilisation categories and power ratings
Rated for AC-3, AC-3e, AC-1, AC-5a, AC-5b, AC-6a, AC-6b, DC-1, DC-3, and DC-5 – this contactor covers motor starting, resistive, and DC load switching. At 460/480 V 60 Hz it handles 250 hp; at 575/600 V, 300 hp. The AC-1 thermal current (Ith) is 440 A per pole, dissipating 30 W per pole.
Mechanical durability and robustness
Mechanical life is 8 million cycles. The contactor withstands vibration up to 4 gn (closed) and shock 15 gn for 11 ms (closed), making it suitable for high-vibration environments like compressors or conveyors.
Listed as current production. No end-of-life notice or phase-out indicated. The part is specified into the BOM and available to quote against a purchase order through our distribution channel.
Meets EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Also listed for UL 60335-1 and UL 60335-2-40 Annex JJ for appliance applications. IP2X front face with shrouds.