Skip to main content
Schneider Electric LC1G330EHEA

Schneider Electric LC1G330EHEA TeSys Giga Contactor, 160 kW

MPNLC1G330EHEA
Active

Schneider Electric TeSys Giga contactor, LC1G330EHEA, 3-pole, 48-130 V AC/DC coil, 160 kW at 400 V AC-3e, dark grey.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G330EHEA key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage48...130 V AC 50/60 Hz 48...130 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current2.65 kA - 10 s 1.8 kA - 30 s 1.3 kA - 1 min 0.9 kA - 3 min 0.75 kA - 10 min
Breaking capacity2940 A at 440 V
[Ie] rated operational current440 A (at 330 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Ith] conventional free air thermal current440 A (at 104 °F (40 °C))
Motor power90 kW at 230 V AC 50/60 Hz (AC-3e) 160 kW at 400 V AC 50/60 Hz (AC-3e) 160 kW at 415 V AC 50/60 Hz (AC-3e) 185 kW at 440 V AC 50/60 Hz (AC-3e) 200 kW at 500 V AC 50/60 Hz (AC-3e) 220 kW at 690 V AC 50/60 Hz (AC-3e) 185 kW at 1000 V AC 50/60 Hz (AC-3e) 90 kW at 230 V AC 50/60 Hz (AC-3) 160 kW at 400 V AC 50/60 Hz (AC-3) 160 kW at 415 V AC 50/60 Hz (AC-3) 200 kW at 440 V AC 50/60 Hz (AC-3) 200 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 90 kW at 230 V AC 50/60 Hz (AC-4) 160 kW at 400 V AC 50/60 Hz (AC-4) 160 kW at 415 V AC 50/60 Hz (AC-4) 185 kW at 440 V AC 50/60 Hz (AC-4) 200 kW at 500 V AC 50/60 Hz (AC-4) 220 kW at 690 V AC 50/60 Hz (AC-4) 185 kW at 1000 V AC 50/60 Hz (AC-4)

All specifications

LC1G330EHEA additional specifications
ParameterValue
Inrush power in360 W
Maximum horse power rating100 hp at 200/208 V 60 Hz 125 hp at 230/240 V 60 Hz 250 hp at 460/480 V 60 Hz 300 hp at 575/600 V 60 Hz
Power dissipation per pole30 W AC-1 - Ith 440 A 16 W AC-3 - Ith 330 A
Inrush power in VA (50/60 hz, AC)430 VA
Hold-in power consumption in9.0 W
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width5.5 in (140 mm)
Height11.4 in (290 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.000144 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching Motor control
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating400 A aM at 250 A aM at 500 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity3830 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

Motor load rating

The Schneider Electric LC1G330EHEA is a 3-pole TeSys Giga contactor rated for 160 kW at 400 V AC-3e, with a 48-130 V AC/DC coil – that coil range covers most North American and European control voltages without a tap change. Motor power spans 90 kW at 230 V up to 220 kW at 690 V AC-3e, so it's sized for a big pump or compressor line. Mechanical durability is 8 Mcycles.

Mount and wire

Mounts on a plate; the power connections accept busbars up to 32x10 mm or lugs for 185 mm² cable. Control circuit uses push-in terminals for 0.2-2.5 mm² solid or stranded. Tightening torque for power connections is 35 Nm – that's a beefy 3/8-inch hex driver. Depth of 8.9 in (226 mm) fits standard deep enclosures; overall dimensions are 11.4 in high and 5.5 in wide.

Compliance pack

Carries EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, plus IEC 60335 for appliance isolation. That's a broad certification stack for export or domestic builds.

Frequently asked questions

What is the color of the LC1G330EHEA?

Dark grey.

What is the depth of the LC1G330EHEA?

8.9 in (226 mm).

What compliance documentation is available for the LC1G330EHEA?

It is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and IEC 60335-1 Clause 30.2 among others.

MPN
LC1G330EHEA