Specifications

LC1G330LSEA key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage200...500 V AC 50/60 Hz 200...500 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current2.65 kA - 10 s 1.8 kA - 30 s 1.3 kA - 1 min 0.9 kA - 3 min 0.75 kA - 10 min
Breaking capacity2940 A at 440 V
[Ie] rated operational current440 A (at 330 A (at <140 °F (60 °C)) at <= 440 V AC-3
Motor power90 kW at 230 V AC 50/60 Hz (AC-3e) 160 kW at 400 V AC 50/60 Hz (AC-3e) 160 kW at 415 V AC 50/60 Hz (AC-3e) 185 kW at 440 V AC 50/60 Hz (AC-3e) 200 kW at 500 V AC 50/60 Hz (AC-3e) 220 kW at 690 V AC 50/60 Hz (AC-3e) 185 kW at 1000 V AC 50/60 Hz (AC-3e) 90 kW at 230 V AC 50/60 Hz (AC-3) 160 kW at 400 V AC 50/60 Hz (AC-3) 160 kW at 415 V AC 50/60 Hz (AC-3) 200 kW at 440 V AC 50/60 Hz (AC-3) 200 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 90 kW at 230 V AC 50/60 Hz (AC-4) 160 kW at 400 V AC 50/60 Hz (AC-4) 160 kW at 415 V AC 50/60 Hz (AC-4) 185 kW at 440 V AC 50/60 Hz (AC-4) 200 kW at 500 V AC 50/60 Hz (AC-4) 220 kW at 690 V AC 50/60 Hz (AC-4) 185 kW at 1000 V AC 50/60 Hz (AC-4)
Inrush power in300 W

All specifications

LC1G330LSEA additional specifications
ParameterValue
Maximum horse power rating100 hp at 200/208 V 60 Hz 125 hp at 230/240 V 60 Hz 250 hp at 460/480 V 60 Hz 300 hp at 575/600 V 60 Hz
Power dissipation per pole30 W AC-1 - Ith 440 A 16 W AC-3 - Ith 330 A
Inrush power in VA (50/60 hz, AC)530 VA
Hold-in power consumption in9.0 W
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width5.5 in (140 mm)
Height11.4 in (290 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.000144 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching Motor control
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating400 A aM at 250 A aM at 500 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc
MPN