Skip to main content
Schneider Electric LC1G4004EHEA

Schneider LC1G4004EHEA TeSys Giga 4P Contactor, 1000V

MPNLC1G4004EHEA
Obsolete

Schneider TeSys Giga LC1G4004EHEA 4-pole contactor, 48-130 V AC/DC coil, rated insulation 1000 V, 8 Mcycles mechanical durability.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G4004EHEA key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage48...130 V AC 50/60 Hz 48...130 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min
Breaking capacity3480 A at 440 V
[Ie] rated operational current400 A (at 550 A (at <104 °F (40 °C)) at <= 1000 V AC-1
[Ith] conventional free air thermal current550 A (at 104 °F (40 °C))
Inrush power in360 W

All specifications

LC1G4004EHEA additional specifications
ParameterValue
Maximum horse power rating125 hp at 200/208 V 60 Hz 150 hp at 230/240 V 60 Hz 300 hp at 460/480 V 60 Hz 400 hp at 575/600 V 60 Hz
Power dissipation per pole30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A
Inrush power in VA (50/60 hz, AC)450 VA
Hold-in power consumption in8.3 W
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width7.3 in (185 mm)
Height11.4 in (290 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.0001 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity5090 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

TeSys Giga 4P power contactor

The control circuit accepts 48 to 130 V AC or DC with built-in bidirectional peak limiting — no external suppressor needed. Mechanical durability is 8 million cycles, but keep the operating rate under 600 cycles per hour for AC-3 duty to get that life.

Ratings that matter for selection

Making capacity 5090 A at 440 V and breaking capacity 3480 A. Power dissipation runs 30 W at Ith 550 A AC-1, 16 W at Ith 400 A AC-3; connection pitch 45 mm, busbar up to 32 x 10 mm, lugs to 185 mm², push-in control wires 0.2–2.5 mm², torque 35 N·m (309.8 lbf·in).

The contactor carries certifications under EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and UL 60335-1. Front face with shrouds gives IP2X protection per IEC 60529 and VDE 0106. Protective treatment is TH (tropicalized). These marks cover the regulatory needs for most industrial panels in North America, Europe, and Japan.

Frequently asked questions

What is the listed color of the LC1G4004EHEA?

Dark grey.

What is the depth of the LC1G4004EHEA?

8.9 inches (226 mm).

What compliance documentation does the LC1G4004EHEA carry?

It complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and UL 60335-1. Protective treatment is TH (tropicalized).

MPN
LC1G4004EHEA