What the LC1G400BEEA is for
Its built-in bidirectional peak limiting coil suppresses voltage spikes without external snubbers, simplifying wiring on inductive loads. With motor power ratings up to 315 kW at 690 V AC-3, it fits large pump, compressor, and conveyor drives. The coil accepts 24...48 V AC or DC, common across industrial control circuits.
The LC1G400BEEA carries approvals under EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and several IEC 60335 appliance standards. That covers global panel acceptance from IEC markets to North American UL-listed equipment.
Plate-mounted at 45 mm pitch; power terminals accept bar 32x10 mm or ring lugs 185 mm² (torque 35 N·m). Control push-in wiring for 0.2-2.5 mm²; IP2X front with shrouds; dimensions 226x140x290 mm; 8 Mcycles mechanical endurance.