Skip to main content
Schneider Electric LC1G400KUEN

Schneider Electric LC1G400KUEN

MPNLC1G400KUEN
Active

LC1G400KUEN - HIGH POWER by SCHNEIDER ELECTRIC

$548.64Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G400KUEN key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage100...250 V AC 50/60 Hz 100...250 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min
Breaking capacity3480 A at 440 V
[Ie] rated operational current550 A (at 400 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Ith] conventional free air thermal current550 A (at 104 °F (40 °C))
Motor power110 kW at 230 V AC 50/60 Hz (AC-3e) 200 kW at 400 V AC 50/60 Hz (AC-3e) 200 kW at 415 V AC 50/60 Hz (AC-3e) 250 kW at 440 V AC 50/60 Hz (AC-3e) 250 kW at 500 V AC 50/60 Hz (AC-3e) 315 kW at 690 V AC 50/60 Hz (AC-3e) 220 kW at 1000 V AC 50/60 Hz (AC-3e) 110 kW at 230 V AC 50/60 Hz (AC-3) 200 kW at 400 V AC 50/60 Hz (AC-3) 200 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 500 V AC 50/60 Hz (AC-3) 315 kW at 690 V AC 50/60 Hz (AC-3) 220 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 230 V AC 50/60 Hz (AC-4) 200 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 415 V AC 50/60 Hz (AC-4) 220 kW at 440 V AC 50/60 Hz (AC-4) 250 kW at 500 V AC 50/60 Hz (AC-4) 315 kW at 690 V AC 50/60 Hz (AC-4) 220 kW at 1000 V AC 50/60 Hz (AC-4)

All specifications

LC1G400KUEN additional specifications
ParameterValue
Inrush power in660 W
Maximum horse power rating125 hp at 200/208 V 60 Hz 150 hp at 230/240 V 60 Hz 300 hp at 460/480 V 60 Hz 400 hp at 575/600 V 60 Hz
Power dissipation per pole30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A
Inrush power in VA (50/60 hz, AC)750 VA
Hold-in power consumption in9.3 W
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width5.5 in (140 mm)
Height8.9 in (225 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.0001 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching Motor control
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity5090 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc
MPN