Schneider LC1G5004KUEN TeSys Giga contactor, 500 A AC-3, 100 V coil

MPNLC1G5004KUEN
Active

Schneider Electric TeSys Giga LC1G5004KUEN 4-pole contactor, 500 A AC-3 switching current, 100 V coil, 4.6 kA breaking capacity, plate mount, IP2X front face.

$3,967.92 – $4,616.57Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G5004KUEN key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage100...250 V AC 50/60 Hz 100...250 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current4.0 kA - 10 s 2.8 kA - 30 s 2.2 kA - 1 min 1.5 kA - 3 min 1.2 kA - 10 min
Breaking capacity4600 A at 440 V
[Ie] rated operational current500 A (at 700 A (at <104 °F (40 °C)) at <= 1000 V AC-1
[Ith] conventional free air thermal current700 A (at 104 °F (40 °C))
Inrush power in660 W

All specifications

LC1G5004KUEN additional specifications
ParameterValue
Power dissipation per pole40 W AC-1 - Ith 700 A 20 W AC-3 - Ith 500 A
Inrush power in VA (50/60 hz, AC)750 VA
Hold-in power consumption in9.3 W
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width7.3 in (185 mm)
Height8.9 in (225 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.00008 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating500 A aM at 400 A aM at 800 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity5090 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

Overview

The LC1G5004KUEN is a Schneider TeSys Giga 4-pole contactor rated for 500 A AC-3 switching with a 100 V coil, built for heavy motor and power-switching duty. It carries a 4.6 kA breaking capacity (Icu) and is certified to EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, covering global panel builds.

The 500 A AC-3 rating suits large induction motors; the 4.6 kA Icu gives headroom for high-fault-capacity installations.

MPN