Skip to main content
Schneider Electric LC1G500BEEA

TeSys Giga LC1G500BEEA 3-Pole Contactor, 355 kW AC-3e

MPNLC1G500BEEA
Active

TeSys Giga, 3-pole contactor, LC1G500BEEA, 355 kW at 690 V AC-3e, coil 24-48 V AC/DC, dark grey.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1G500BEEA key specifications
ParameterValue
Range of productTeSys Giga
Product or component typeContactor
Coil voltage24...48 V AC 50/60 Hz 24...48 V DC
Voltage1000 V
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current4.0 kA - 10 s 2.8 kA - 30 s 2.2 kA - 1 min 1.5 kA - 3 min 1.2 kA - 10 min
Breaking capacity4600 A at 440 V
[Ie] rated operational current700 A (at 500 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Ith] conventional free air thermal current700 A (at 104 °F (40 °C))
Motor power147 kW at 230 V AC 50/60 Hz (AC-3e) 250 kW at 400 V AC 50/60 Hz (AC-3e) 250 kW at 415 V AC 50/60 Hz (AC-3e) 280 kW at 440 V AC 50/60 Hz (AC-3e) 315 kW at 500 V AC 50/60 Hz (AC-3e) 355 kW at 690 V AC 50/60 Hz (AC-3e) 335 kW at 1000 V AC 50/60 Hz (AC-3e) 160 kW at 230 V AC 50/60 Hz (AC-3) 250 kW at 400 V AC 50/60 Hz (AC-3) 250 kW at 415 V AC 50/60 Hz (AC-3) 315 kW at 440 V AC 50/60 Hz (AC-3) 355 kW at 500 V AC 50/60 Hz (AC-3) 355 kW at 690 V AC 50/60 Hz (AC-3) 335 kW at 1000 V AC 50/60 Hz (AC-3) 150 kW at 230 V AC 50/60 Hz (AC-4) 250 kW at 400 V AC 50/60 Hz (AC-4) 250 kW at 415 V AC 50/60 Hz (AC-4) 295 kW at 440 V AC 50/60 Hz (AC-4) 295 kW at 500 V AC 50/60 Hz (AC-4) 355 kW at 690 V AC 50/60 Hz (AC-4) 280 kW at 1000 V AC 50/60 Hz (AC-4)

All specifications

LC1G500BEEA additional specifications
ParameterValue
Inrush power in350 W
Maximum horse power rating150 hp at 200/208 V 60 Hz 200 hp at 230/240 V 60 Hz 400 hp at 460/480 V 60 Hz 450 hp at 575/600 V 60 Hz
Power dissipation per pole40 W AC-1 - Ith 700 A 20 W AC-3 - Ith 500 A
Inrush power in VA (50/60 hz, AC)490 VA
Hold-in power consumption in6.0 W
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connection pitch1.8 in (45 mm)
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end
ColorDark grey
Depth8.9 in (226 mm)
Width5.5 in (140 mm)
Height11.4 in (290 mm)
Mechanical durability8 Mcycles
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ
RangeTeSys
CategoryUS10I1222329
Operating time40...70 ms closing 15...50 ms opening
Coil technologyBuilt-in bidirectional peak limiting
Average impedance0.00008 Ohm
Device short nameLC1G
Tightening torque309.8 lbf.in (35 N.m)
Compatibility codeLC1G
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationPower switching Motor control
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Associated fuse rating500 A aM at 400 A aM at 800 A gG at 600 A UL Type L at <= 600 V
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4
Safety reliability levelB10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity5090 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

Mounting and fit

The LC1G500BEEA: Plate-mount contactor: 226 mm deep, 140 mm wide, 290 mm tall. The 45 mm pole pitch keeps wiring orderly. Power terminals accept bar up to 32×10 mm or ring lugs up to 185 mm²; control terminals push-in for solid or ferruled stranded 0.2-2.5 mm².

Performance under duty

Rated breaking capacity 4600 A at 440 V; making capacity 5090 A — handles inrush on large motors without contact weld. Power dissipation per pole: 40 W at AC-1 (Ith 700 A), 20 W at AC-3 (Ith 500 A). Heat budget can be estimated for panel cooling. Coil technology includes built-in bidirectional peak limiting, so the inrush power at 350 W DC is controlled and does not stress the control transformer.

Frequently asked questions

What is LC1G500BEEA's listed color?

Dark grey.

What is LC1G500BEEA's listed depth?

226 mm (8.9 in).

What compliance documentation does the manufacturer provide for LC1G500BEEA?

It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, IEC 60335-1 Clause 30.2, IEC 60335-2-40 Annex JJ, UL 60335-1, and UL 60335-2-40 Annex JJ.

MPN