Skip to main content
Schneider Electric LC1K06016FLS207 — Contactors

Schneider TeSys LC1K06016FLS207 Contactor, 3P, 1.8W Coil

MPNLC1K06016FLS207
Obsolete

Schneider Electric TeSys LC1K series, 3-pole contactor, LC1K06016FLS207, 1.8 W coil with integral suppression, 1 NC auxiliary contact, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1K06016FLS207 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control
LC1K06016FLS207 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-4
LC1K06016FLS207 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K06016FLS207 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV0 conforming to UL 94
LC1K06016FLS207 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LC1K06016FLS207 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric TeSys LC1K06016FLS207 is a 3-pole contactor with a 1.8 W coil that includes an integral suppression device, rated for motor control in AC-3, AC-3e, and AC-4 utilization categories. It carries one normally closed (1 NC) instantaneous auxiliary contact alongside the three NO main power poles, which is typical for a holding-circuit interlock or status feedback.

Rated for AC-3 and AC-4 duty per IEC 60947-4-1, this contactor is sized for switching motor loads under both normal running (AC-3) and inching/plugging (AC-4) conditions — a distinction that matters when the application includes frequent jogging or reversing. The 1.8 W inrush and hold-in power at 20 °C means the coil driver sees a modest load, and the integral suppression device handles the back-EMF spike, so no external flyback diode or RC snubber is needed across the coil terminals. Electrical durability is listed at 1.3 million cycles at 6 A AC-3 up to 440 V, with mechanical durability at 30 million cycles — the electrical figure is the limiting factor for motor-load life, while the mechanical figure governs auxiliary-signal or low-current use.

Power-circuit connections use lugs or ring terminals with a tightening torque of 0.8 to 1.3 N·m, compatible with a 3.2 mm flat, Philips No 2, or Pozidriv No 2 screwdriver. The 57 mm depth and 58 mm height should be checked against enclosure depth limits, especially when mounted with an overload relay or auxiliary block alongside.

Certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1, covering the major global markets for motor-contactor applications. Flame retardance is V0 per UL 94, and the protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance.

Frequently asked questions

What is the closest pin-compatible alternative in this family?

Within the TeSys LC1K series, the closest alternative would be a contactor with the same 3-pole, 1 NC auxiliary configuration but a different coil voltage rating — the coil voltage is encoded in the suffix of the order code. For a direct form-fit-function swap, match the coil voltage and auxiliary count exactly.

What compliance documentation does this part carry?

The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. Flame retardance is V0 per UL 94.

What is the depth of this contactor?

The depth is 57 mm, with a width of 45 mm and a height of 58 mm.

MPN