Skip to main content
Schneider Electric LC1K06016Q7 — Contactors

Schneider TeSys K LC1K06016Q7 Contactor, 3P, 6 A, 380-400 VA

MPNLC1K06016Q7
Obsolete

Schneider Electric TeSys K contactor, 3P, AC-3 <= 440 V 6 A, 1 NC auxiliary contact, 380...400 V AC coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K06016Q7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K06016Q7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-3
LC1K06016Q7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K06016Q7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K06016Q7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K06016Q7 — Other specifications
ParameterValue
Motor power1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current6 A at 10 MOhm for signalling circuit
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit

Product details

The motor power table tells the real story: 1.5 kW at 220-230 V, 2.2 kW at 380-415 V, and 3 kW at 440-690 V. That spread covers standard three-phase induction motors across common line voltages. The 380-400 V AC coil is the control voltage; it pulls in reliably at that nominal level. The 1 NC auxiliary contact is built in — no add-on block needed for a basic feedback or interlock. Heat dissipation is 1.3 W, which is low enough that panel ventilation isn't a concern for this part alone. The 57 mm depth and 45 mm width fit a standard DIN-rail footprint; it snaps onto the rail and occupies about the space of a miniature circuit breaker.

Frequently asked questions

What are the key ratings for this contactor?

3-pole, AC-3 rated operational current of 6 A at 440 V. Motor power ranges from 1.5 kW at 220-230 V to 3 kW at 440-690 V. Coil is 380-400 V AC. Includes 1 NC auxiliary contact.

What is the physical size of the LC1K06016Q7?

Depth 57 mm, width 45 mm, height 58 mm. It mounts on a standard DIN rail.

MPN