Schneider Electric LC1K0610P72TQ — Contactors

Schneider Electric LC1K0610P72TQ TeSys K Contactor, 6 A, 230

MPNLC1K0610P72TQ
Obsolete

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 6 A, 1 NO auxiliary contact, 230 V AC coil, TQ packaging.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K0610P72TQ — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K0610P72TQ — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-3
LC1K0610P72TQ — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K0610P72TQ — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K0610P72TQ — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LC1K0610P72TQ is a TeSys K three-pole contactor from Schneider Electric, rated for control applications in AC-3 and AC-4 utilisation categories. It switches motor loads up to 6 A at ≤440 V AC-3, which translates to 1.5 kW at 220–230 V, 2.2 kW at 380–415 V, and 3 kW at 480 V — the rating that governs fit for a given motor nameplate. The 230 V AC coil includes a built-in bidirectional peak limiting diode suppressor, so you don't need to add an external snubber across the coil terminals.

AC-4 (plugging/reversing) duty is also listed, but the current must be derated for frequent jogging. The 1 NO auxiliary contact is built in, so you get one feedback signal back to the PLC without adding a side-mount block. Coil dissipation is 1.3 W, negligible for panel thermal budget. Flame retardance meets V1 per UL 94 and Class 2 per NF F 16-101/102, which covers rail and building-material fire safety requirements.

Physical integration

The TQ packaging (bulk pack) means it ships without individual retail carton.

Frequently asked questions

What is the closest alternative to the LC1K0610P72TQ?

There is no official pin-compatible successor from Schneider. For new designs, the current TeSys D range offers similar ratings but with a different footprint and terminal layout. Verify panel dimensions before substituting.

What motor power can this contactor switch?

Up to 1.5 kW at 220–230 V, 2.2 kW at 380–415 V, and 3 kW at 480 V AC, all at 50/60 Hz. These are AC-3 duty ratings for standard squirrel-cage motors.

Does the coil need an external suppression circuit?

No. The built-in bidirectional peak limiting diode suppressor handles coil transient suppression. Just ensure polarity is correct if the circuit uses a DC control signal.

MPN
LC1K0610P72TQ