Skip to main content
Schneider Electric LC1K09013Q7 — Contactors

Schneider TeSys K LC1K09013Q7 Contactor, 3P, 9A AC-3, 380-40

MPNLC1K09013Q7
Obsolete

Schneider Electric TeSys K contactor, 3 poles, AC-3 9 A at ≤440 V, 380…400 V AC 50/60 Hz coil, 1 NC auxiliary contact.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K09013Q7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K09013Q7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-1 AC-4
LC1K09013Q7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K09013Q7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K09013Q7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K09013Q7 — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Device short nameLC1K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit

Product details

The Schneider TeSys K LC1K09013Q7 is a 3-pole contactor rated for motor switching in AC-3 duty at 9 A up to 440 V, with a 380…400 V AC 50/60 Hz coil. It carries one normally-closed auxiliary contact. The AC-3 rating means it handles the inrush of a squirrel-cage induction motor during starting and breaks the running current — the standard utilisation category for motor contactors. Motor power capability spans the voltage range: 2.2 kW at 220…230 V, 4 kW at 380…415 V, 4 kW at 440 V, 4 kW at 480 V, and 4 kW at 500…600 V and 660…690 V, all at 50/60 Hz. This means the contactor delivers the same 4 kW motor rating across most common European and North American industrial voltages above 380 V, simplifying BOM planning when line voltage varies by site.

No broker or surplus hunt is needed. The TeSys K family is widely stocked, so lead times are typically short, but as with any active line, a firm RFQ confirms the current allocation.

Frequently asked questions

What are the key ratings I need to know for motor switching?

The contactor is rated 9 A in AC-3 duty at ≤440 V, which translates to 4 kW motor power at 380…415 V, 440 V, 480 V, 500…600 V, and 660…690 V (all at 50/60 Hz). At 220…230 V the motor power rating drops to 2.2 kW. The coil is 380…400 V AC 50/60 Hz.

Does the LC1K09013Q7 carry flame-retardance approvals for rail or transit applications?

Yes. It meets V1 per UL 94 and Requirement 2 per NF F 16-101 and NF F 16-102, making it suitable for rolling-stock and public-transport equipment where fire-smoke-toxicity compliance is required.