Schneider Electric LC1K09015J7 — Contactors

Schneider TeSys K LC1K09015J7 Contactor, 3P, 9A AC-3, 12V AC

MPNLC1K09015J7
Active

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 9 A, 1 NC auxiliary contact, 12 V AC coil, 45 x 57 x 58 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K09015J7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K09015J7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-4 AC-1
LC1K09015J7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K09015J7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K09015J7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K09015J7 — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Device short nameLC1K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit

Product details

Motor power ratings span from 2.2 kW at 220…230 V AC up to 4 kW at 480 V, 500…600 V, and 660…690 V AC, all at 50/60 Hz. The 4 kW rating at 480 V is the most common North American selection point; the 4 kW at 400 V class covers European 400 V three-phase networks.

The same contactor also carries AC-1 (resistive) and AC-4 (inching/plugging) utilisation categories, so it can handle resistive heater loads or frequent reversing duty, but the AC-3 figure is the one to match against your motor nameplate FLA. Short-time withstand ratings (Icw) are given for the power circuit: 90 A for 1 second, stepping down to 20 A for 15 minutes or longer. These numbers tell you the contactor can ride through a short-duration fault without welding its contacts — useful for coordination studies on a motor branch circuit.

Frequently asked questions

What are the key ratings I need to match for a motor starter application?

The critical figure is the AC-3 rated operational current of 9 A at ≤440 V, which corresponds to motor power ratings of 4 kW at 480 V and 2.2 kW at 220…230 V. The coil is 12 V AC. The contactor has 3 NO power poles and 1 NC auxiliary contact.

What is the physical size of this contactor?

Width is 45 mm, depth is 57 mm, height is 58 mm. It mounts on a 35 mm DIN rail.

MPN
LC1K09015J7