Skip to main content
Schneider Electric LC1K09105R7 — Contactors

Schneider LC1K09105R7 TeSys K Contactor, 9A AC-3, 440V AC Co

MPNLC1K09105R7
Active

Schneider Electric TeSys K contactor, 3P, AC-3 <= 440 V 9 A, 1 NO aux., 440 V AC coil, obsolete status.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K09105R7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K09105R7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-1 AC-4 AC-3
LC1K09105R7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K09105R7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K09105R7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K09105R7 — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit

Product details

Part identity and key ratings

The Schneider LC1K09105R7 is a TeSys K three-pole contactor rated for AC-3 duty at 9 A up to 440 V, with a 440 V AC coil and one normally open auxiliary contact. The AC-3 category means it is designed for starting and stopping squirrel-cage motors under load — the 9 A figure governs the motor current it can switch, not resistive heating. Motor power capability spans 2.2 kW at 220–230 V AC up to 4 kW across 380–690 V AC 50/60 Hz supplies, covering common European and North American line voltages. The AC-4 utilisation category also applies, so the contactor can handle plugging and inching duty cycles where the motor is reversed or jogged under load.

This order code is marked obsolete by the manufacturer. No official successor order code is listed, so a parametric cross-reference to a current TeSys K or TeSys D variant requires verifying the coil voltage, pole count, and auxiliary configuration against the replacement candidate's datasheet.

Frequently asked questions

What are the key ratings of the LC1K09105R7?

It is a 3-pole contactor rated 9 A in AC-3 (motor switching) up to 440 V, with a 440 V AC coil and one NO auxiliary contact. Motor power ranges from 2.2 kW at 220–230 V to 4 kW at 380–690 V AC.

What compliance documentation applies to this part?

The contactor meets UL 94 V1 flame retardance and NF F 16-101/102 Requirement 2 for fire behaviour. As a Schneider TeSys K product, it is designed to applicable IEC/EN standards for contactors.

How do I source the LC1K09105R7 now that it is obsolete?

We source it to order against an RFQ through surplus and broker channels. Submit an RFQ with your target quantity and delivery window, and we will confirm availability and pricing.

MPN