Skip to main content
Schneider Electric LC1K09105V7TQ — Contactors

Schneider TeSys K LC1K09105V7TQ Contactor, 9 A AC-3, 400 V C

MPNLC1K09105V7TQ
Obsolete

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 9 A, 1 NO auxiliary, 400 V AC coil, TQ packaging.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K09105V7TQ — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K09105V7TQ — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-4 AC-1
LC1K09105V7TQ — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K09105V7TQ — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K09105V7TQ — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K09105V7TQ — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Device short nameLC1K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit

Product details

The LC1K09105V7TQ is a TeSys K three-pole contactor from Schneider Electric, rated 9 A in AC-3 utilisation category at ≤440 V, with a 400 V AC coil and one normally open auxiliary contact. It's designed for control applications — switching motor loads, resistive heaters, or other inductive circuits in panel builds. The contactor carries motor power ratings across common supply voltages: 2.2 kW at 220–230 V AC, 4 kW at 380–415 V, 4 kW at 440 V, 4 kW at 480 V, and 4 kW at 500–600 V and 660–690 V, all at 50/60 Hz.

Sourcing reality — obsolete, sourced to order

The LC1K09105V7TQ is obsolete. No official successor order code from Schneider is available. For a drop-in, verify pinout and footprint against your panel layout.

The contactor also carries AC-4 (inching/plugging) and AC-1 (resistive) utilisation categories, so it can handle duty-cycle applications beyond simple on/off motor starting. Short-time withstand current (Icw) is specified for the power circuit: 90 A for 1 s, 85 A for 5 s, 80 A for 10 s, down to 20 A for ≥15 min at 50 °C. This tells you the contactor can survive fault currents long enough for an upstream protective device to clear — useful when coordinating with a motor circuit breaker or fuse. Flame retardance meets V1 per UL 94, plus Requirement 2 per NF F 16-101 and NF F 16-102 — relevant for rail or transit applications where fire-smoke-toxicity standards apply.

Physical integration

Pole composition is 3 NO (three normally open main poles), with one NO auxiliary contact built in. The coil is 400 V AC — verify your control circuit voltage matches.

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current is 9 A in AC-3 at ≤440 V. Motor power ranges from 2.2 kW at 220–230 V up to 4 kW at 480–690 V. Coil is 400 V AC. Short-time withstand current is 90 A for 1 s on the power circuit.

MPN
LC1K09105V7TQ