Skip to main content
Schneider Electric LC1K09107P72 — Contactors

Schneider TeSys K LC1K09107P72 Contactor, 9 A AC-3, 230 V AC

MPNLC1K09107P72
Obsolete

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 9 A, 1 NO aux., 230 V AC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K09107P72 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K09107P72 — Ratings & Performance
ParameterValue
Utilisation categoryAC-1 AC-3 AC-4
LC1K09107P72 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K09107P72 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K09107P72 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K09107P72 — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Heat dissipation1.3 W
Range of productTeSys K
Device short nameLC1K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit

Product details

The LC1K09107P72 is a TeSys K three-pole contactor from Schneider Electric, rated for 9 A in AC-3 utilisation category at ≤440 V. That AC-3 rating governs switching of squirrel-cage motors — the 9 A figure is the current the main poles can make and break under motor starting conditions, not the continuous thermal current. For a 230 V AC coil with built-in bidirectional peak limiting diode suppression, this part was sized into control panels for small motor loads up to 4 kW at 480 V.

Motor power ratings span 2.2 kW at 220–230 V up to 4 kW at 480 V and 660–690 V, all at 50/60 Hz. That 4 kW at 480 V is the typical sizing point for a 5 HP motor on a 480 V three-phase system — the contactor's AC-3 current rating of 9 A is the limiting factor, not the power figure. The 57 mm depth and 45 mm width fit the standard DIN-rail footprint of the TeSys K range, so panel cut-outs and busbar layouts from existing designs carry over.

Frequently asked questions

What is the closest alternative to the LC1K09107P72 in the TeSys family?

The TeSys K range includes current-production contactors with the same 45 mm width and 3-pole form factor, but coil voltage and auxiliary contact configuration must match. There is no single pin-compatible drop-in listed as an official successor. A parametric search within the TeSys K series for a 3P contactor with 9 A AC-3 rating and 230 V AC coil will yield candidates, but the mounting hole pattern and terminal layout should be verified against the existing panel design.

What compliance documentation is available for this contactor?

The part carries a V1 flame retardance rating per UL 94 and meets NF F 16-101 and NF F 16-102 Requirement 2 for railway fire behaviour. Standard Schneider documentation for the TeSys K range includes the datasheet and declaration of conformity; specific RoHS or REACH statements would be part of the manufacturer's product compliance package.

MPN
LC1K09107P72