Skip to main content
Schneider Electric LC1K12004N7 — Contactors

TeSys K LC1K12004N7 4P Contactor, 20 A AC-1, 400-415 V AC Co

MPNLC1K12004N7
Obsolete

Schneider Electric TeSys K contactor, 4P (4 NO), AC-1 20 A at ≤440 V, 400-415 V AC 50/60 Hz coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K12004N7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1K12004N7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-1
LC1K12004N7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1K12004N7 — Environmental
ParameterValue
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K12004N7 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LC1K12004N7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K12004N7 is a TeSys K 4-pole contactor with 4 normally-open power poles, a 400-415 V AC 50/60 Hz coil, and a rated operational current of 20 A in AC-1 duty at ≤440 V. It is designed for switching resistive loads in control panels and is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1.

The 20 A AC-1 rating at ≤440 V is the thermal current the contactor can carry continuously in resistive load circuits. For motor loads, the AC-3 rating would be lower — this part is specced for resistive duty, so do not size it for motor starting without checking the manufacturer's derating. The 400-415 V AC coil means it pulls in reliably on a 400 V line, with a hold-in consumption of 4.5 VA and inrush of 30 VA at 20 °C. The 1.3 W heat dissipation matters for enclosure thermal budgeting, especially in a crowded DIN-rail panel.

The 4 NO pole configuration with a 400 V coil is common in heating and lighting contactor panels. The associated fuse rating is 25 A gG or 25 A aM for the power circuit. Mechanical robustness is rated for 10-15 Gn shock and 4 Gn vibration with the contactor closed, suitable for industrial environments.

Frequently asked questions

What are the key ratings for this contactor?

The LC1K12004N7 is rated 20 A in AC-1 duty at ≤440 V with a 400-415 V AC 50/60 Hz coil. It has 4 normally-open poles and dissipates 1.3 W.

What compliance standards does this contactor meet?

It is certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. The enclosure material is rated V1 per UL 94.

How do I source this obsolete part?

We source it to order against an RFQ through surplus and broker channels. Submit an RFQ for current availability and pricing.

MPN
LC1K12004N7