Skip to main content
Schneider Electric LC1K12016SLS207 — Contactors

Schneider TeSys K LC1K12016SLS207 Contactor, 12A AC-3, 72V D

MPNLC1K12016SLS207
Obsolete

Schneider Electric TeSys K contactor, LC1K12016SLS207, 3-pole, AC-3 ≤440V 12A, 1NC auxiliary contact, 72V DC low consumption coil with integral suppression.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K12016SLS207 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load

Ratings & Performance

LC1K12016SLS207 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-1 AC-4

Contacts & Poles

LC1K12016SLS207 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K12016SLS207 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV0 conforming to UL 94

Approvals

LC1K12016SLS207 — Approvals
ParameterValue
StandardsBS 5424 IEC 60947 NF C 63-110 VDE 0660 IEC 60077-1 IEC 60077-2 EN 45545: R22 HL3 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1K12016SLS207 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K12016SLS207 is a TeSys K contactor, a 3-pole device rated for AC-3 duty at 12 A up to 440 V, with a 72 V DC low-consumption coil that includes an integral suppression diode. The AC-3 rating means it is sized for starting and stopping squirrel-cage motors — the most common industrial motor load — where it makes the inrush and breaks the running current. The 1.8 W hold-in power at 20 °C keeps the panel cool and the power supply budget tight.

The IP20 finger-safe terminals (VDE 0106) are fine for a control cabinet but not for washdown zones. Power connections use ring terminals with a 7 mm outer diameter, torqued to 0.8...1.3 N·m — a standard screwdriver or Pozidriv No 2 handles the job.

Frequently asked questions

What are the key electrical ratings?

Rated 12 A in AC-3 at ≤440 V for motor control, and 20 A in AC-1 for resistive loads. The coil is 72 V DC with a hold-in consumption of 1.8 W at 20 °C. Minimum switching is 5 mA at 17 V for signalling circuits.

What compliance documentation is available?

The contactor is certified to IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN 45545 (R22 HL3). It also meets BS 5424, NF C 63-110, and VDE 0660.

What is the mechanical and electrical durability?

Mechanical durability is 30 million cycles. Electrical durability is 1.3 million cycles at 12 A AC-3 (≤440 V) and 0.3 million cycles at 20 A AC-1.

MPN
LC1K12016SLS207