The coil pulls in on 400-415 VAC 50/60 Hz, so it's sized for European-style 400 V line-to-line control circuits.
Motor power across voltage bands
This contactor covers a wide voltage range for motor loads: 3 kW at 220-230 V, 5.5 kW at 380-415 V and 440 V, and 4 kW at 480 V, 500-600 V, and 660-690 V. That means the same part works on 400 V, 480 V, and 690 V systems — useful if your panel sees mixed voltage feeds or you're stocking a common spare for multiple line voltages.
Rated current and what the utilisation categories mean
The rated operational current (Ie) is 20 A in AC-1 (resistive loads like heaters), 12 A in AC-3 (squirrel-cage motors — starting and disconnecting under load), and 16 A in AC-4 (plugging and inching duty). Heat dissipation is 1.3 W, so it won't cook adjacent components in a dense DIN-rail layout.