Skip to main content
Schneider Electric LC1K12106Q7 — Contactors

Schneider TeSys K LC1K12106Q7 Contactor, 3P, AC-3 12 A, 380-

MPNLC1K12106Q7
Active

Schneider Electric TeSys K contactor, 3 poles, AC-3 ≤440 V 12 A, 1 NO auxiliary, 380-400 V AC coil, 45 x 58 x 57 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K12106Q7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K12106Q7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-1 AC-3
LC1K12106Q7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K12106Q7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K12106Q7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LC1K12106Q7 — Other specifications
ParameterValue
Motor power4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 3 kW at 220...230 V AC 50/60 Hz 5.5 kW at 380...415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz
Heat dissipation1.3 W
Range of productTeSys K
Device short nameLC1K
Compatibility codeLC1K
Device applicationControl
Pole contact composition3 NO
[Ie] rated operational current20 A (at 12 A at 16 A (at 10 MOhm for signalling circuit
[Icw] rated short-time withstand current115 A 50 °C - 1 s for power circuit 105 A 50 °C - 5 s for power circuit 100 A 50 °C - 10 s for power circuit 75 A 50 °C - 30 s for power circuit 55 A 50 °C - 1 min for power circuit 50 A 50 °C - 3 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit 25 A 50 °C - >= 15 min for power circuit

Product details

The TeSys K LC1K12106Q7 is a 3-pole contactor from Schneider Electric's compact TeSys K range, built for control applications. It carries a 380-400 V AC coil and is rated for AC-3 duty at 12 A up to 440 V, meaning it handles motor starting and stopping within that envelope — the AC-3 category covers squirrel-cage motors with switching during running, which is the standard for most conveyor, pump, and fan loads. The same contactor also covers AC-1 (resistive) and AC-4 (plugging/inching) utilisation categories, so it can serve both heater banks and reversing applications. Motor power ratings span from 3 kW at 220-230 V AC up to 5.5 kW at 380-415 V and 440 V, and 4 kW at 480 V through 660-690 V AC. That range covers common low-voltage three-phase supplies across Europe and North America. Heat dissipation is only 1.3 W, which keeps panel temperature rise negligible in a densely packed enclosure.

Integration notes

The 380-400 V AC coil is a standard industrial control voltage across much of Europe and Asia; confirm the control transformer taps before wiring.

Frequently asked questions

What are the key ratings for this contactor?

AC-3 rated operational current is 12 A at ≤440 V. Motor power ranges from 3 kW at 220-230 V up to 5.5 kW at 380-440 V, and 4 kW at 480-690 V. Coil is 380-400 V AC. Short-time withstand current (Icw) is 115 A for 1 second on the power circuit.

What compliance markings does this contactor carry?

Flame retardance is V1 per UL 94, and it also meets NF F 16-101 and NF F 16-102 requirement 2 for railway fire-smoke compliance. The TeSys K range typically carries CE, UL, and CSA certifications; confirm the specific mark for your jurisdiction on the product label.

MPN
LC1K12106Q7