Skip to main content
Schneider Electric LC1K1210U72 — Contactors

TeSys K LC1K1210U72 Contactor, 12 A AC-3, 230-240 VAC Coil

MPNLC1K1210U72
Obsolete

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 12 A, 1 NO aux, 230…240 V AC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K1210U72 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LC1K1210U72 — Ratings & Performance
ParameterValue
Utilisation categoryAC-1 AC-4 AC-3
LC1K1210U72 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K1210U72 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K1210U72 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LC1K1210U72 is a TeSys K 3-pole contactor from Schneider Electric, rated 12 A in AC-3 duty at ≤440 V, with a 230…240 V AC coil. It carries one normally open auxiliary contact and is designed for motor switching in control panels — the AC-3 utilisation category means it handles starting and stopping of squirrel-cage motors under full load. The built-in bidirectional peak-limiting diode suppressor on the coil reduces back-EMF, so the same suppression circuit works regardless of wiring polarity.

Motor power and ratings

Motor power capability varies by line voltage: 3 kW at 220…230 V AC, 5.5 kW at 380…415 V AC, 4 kW at 480 V AC, and 4 kW at 500…600 V AC or 660…690 V AC. The 1.3 W heat dissipation is modest — no forced cooling needed in a standard IP2X enclosure. Short-time withstand current (Icw) for the power circuit is 115 A for 1 s, dropping to 55 A for 1 minute, which gives some headroom for brief overloads during motor start.

Frequently asked questions

What is the closest pin-compatible alternative to LC1K1210U72 in this component family?

There is no official successor order code in the lifecycle record. A current-series TeSys contactor (e.g., TeSys Deca or TeSys F) with the same coil voltage (230…240 V AC), 3-pole configuration, and at least 12 A AC-3 rating would be the functional replacement, but panel footprint and auxiliary wiring must be checked for fit.

What is LC1K1210U72's listed depth?

The depth is 57 mm.

What is LC1K1210U72's listed range?

It belongs to the TeSys K range from Schneider Electric.

MPN
LC1K1210U72