It switches motor loads under AC-3 duty up to 16 A at ≤440 V, and handles resistive loads under AC-1. The coil is 440 V AC. It carries one normally-closed auxiliary contact. Motor power capability spans 4 kW at 480 V AC up to 7.5 kW at 380–415 V AC, covering common three-phase induction motors across European and North American line voltages.
Sourcing reality — obsolete, no official successor
This part is officially obsolete per Schneider Electric's lifecycle status. No direct successor order code is listed.
The 45 mm width occupies one 9 mm module position per pole, typical for this class. Heat dissipation is 1.3 W, low enough that no forced cooling is needed in a standard IP20 control cabinet. The V-0 flame retardance rating per UL 94 means the housing self-extinguishes — a requirement for unventilated enclosures.
Short-circuit and withstand capability
Rated short-time withstand current (Icw) for the power circuit is 115 A for 1 second at 50 °C, tapering to 25 A for 15 minutes or longer. This gives the coordination engineer a curve to size upstream protection — typically a gG fuse or a motor circuit protector set below 115 A.