Schneider Electric LC1K16105FC72 — Contactors

Schneider TeSys K LC1K16105FC72 Contactor, 3P, 16 A, 36 VAC

MPNLC1K16105FC72
Active

Schneider Electric TeSys K contactor, LC1K16105FC72, 3-pole, AC-3 16 A at ≤440 V, 36 V AC coil, built-in peak-limiting diode suppressor.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K16105FC72 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys

Ratings & Performance

LC1K16105FC72 — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-1

Contacts & Poles

LC1K16105FC72 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K16105FC72 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94

Mechanical

LC1K16105FC72 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K16105FC72 is a TeSys K three-pole contactor rated for motor control in AC-3 duty up to 16 A at 440 V, and resistive (AC-1) loads. The 36 V AC coil includes a built-in bidirectional peak-limiting diode suppressor, so you don't need to add an external snubber across the coil terminals. Motor power capability spans 4 kW at 480 V, 5.5 kW at 440 V, and 7.5 kW at 380–415 V, all at 50/60 Hz. That covers most common three-phase motor sizes in a small panel or machine tool. The AC-3 utilisation category is what matters for switching squirrel-cage motors — it means the contactor is tested to make and break locked-rotor current. The AC-1 rating covers resistive heater or lighting loads where the switching stress is lower.

The 1.3 W heat dissipation is low enough that multiple units can be ganged on the rail without forced cooling in a typical enclosure. The housing carries a V1 flame-retardance rating per UL 94, meaning it self-extinguishes within 30 seconds if ignited — a standard requirement for panel components in most industrial control panels.

The rated operational current (Ie) is 16 A in AC-3 at ≤440 V, but the short-time withstand (Icw) tells you what the contacts can survive during a fault: 115 A for 1 second on the power circuit, tapering to 55 A for 1 minute. That 1-second rating is the one to check against upstream breaker coordination — if your branch circuit protective device clears faster than 1 s, you're fine. For a 7.5 kW motor at 380–415 V, the full-load current is around 14–15 A, so this contactor lands right at the sweet spot with a small margin.

Compliance documentation is available from Schneider for RoHS, REACH, and UL/CSA/CE certifications. The V1 flame rating and the built-in coil suppression mean it meets common panel-build requirements without extra components.

Frequently asked questions

What motor sizes does this contactor handle?

It handles 7.5 kW at 380–415 V, 5.5 kW at 440 V, and 4 kW at 480 V or 500–690 V, all at 50/60 Hz AC-3 duty. The 16 A AC-3 rating at ≤440 V is the headline number for motor sizing.

Does the coil need an external suppression diode?

No. The 36 V AC coil has a built-in bidirectional peak-limiting diode suppressor, so you can wire it directly without adding an external snubber or freewheel diode.

What is the physical size for panel layout?

It measures 45 mm wide, 58 mm tall, and 57 mm deep — a standard compact DIN-rail footprint. Heat dissipation is only 1.3 W, so multiple units can be mounted close together.