Schneider Electric LC1K16107C7 — Contactors

Schneider LC1K16107C7 TeSys K Contactor, 3P 16A AC-3, 36V Co

MPNLC1K16107C7
Active

Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 16 A, 1 NO aux., 36 V AC coil.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K16107C7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys

Ratings & Performance

LC1K16107C7 — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-1

Contacts & Poles

LC1K16107C7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K16107C7 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94

Mechanical

LC1K16107C7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

Part identity and motor-duty rating

The LC1K16107C7 is a TeSys K contactor from Schneider Electric, a 3-pole device rated 16 A in AC-3 utilisation category at ≤440 V, with a 36 V AC coil and one normally open auxiliary contact. AC-3 is the standard category for squirrel-cage motor switching — starting, stopping, and inching under load — so the 16 A figure governs the motor current it can handle across a duty cycle, not just resistive make/break.

Motor power coverage by voltage

Motor power capability varies with line voltage: 7.5 kW at 380–415 V AC, 5.5 kW at 440 V, 4 kW at 480 V and at 500–600 V and at 660–690 V, and 4 kW at 220–230 V. This spread covers the common three-phase industrial voltages across 50/60 Hz networks, so the same contactor can be specified for a 400 V class motor in Europe or a 480 V motor in North America without changing the part number.

Panel footprint and thermal management

Heat dissipation is 1.3 W, low enough that derating for mutual heating in a dense enclosure is minimal; no forced ventilation is needed for the contactor itself. The housing carries a V1 flame-retardance rating per UL 94, which satisfies the flammability requirements for most control panels and industrial enclosures.

Short-time withstand and coordination

Rated short-time withstand current (Icw) for the power circuit is 115 A for 1 second, 105 A for 5 seconds, 100 A for 10 seconds, tapering to 25 A for 15 minutes or longer. These values let the contactor ride through downstream faults until an upstream protective device clears — useful when coordinating with a motor circuit protector or fuse. The signalling circuit (auxiliary contact) can handle 110 A for 100 ms, 90 A for 500 ms, and 80 A for 1 second, which covers the inrush from a PLC output or relay driving the coil.

Frequently asked questions

What motor power can this contactor handle at 400 V?

At 380–415 V AC 50/60 Hz, the LC1K16107C7 is rated for 7.5 kW motor power. At 440 V it handles 5.5 kW, and at 480 V it handles 4 kW.

What is the coil voltage for this contactor?

The coil is 36 V AC, as indicated in the order code suffix 7C7.

What is the physical size of the LC1K16107C7?

It measures 45 mm wide, 58 mm high, and 57 mm deep — a compact 3-pole contactor footprint.

Does this contactor have an auxiliary contact?

Yes, it includes one normally open (NO) auxiliary contact built in.