Schneider Electric LC1K1610K72 — Contactors

Schneider TeSys K LC1K1610K72 Contactor, 3P, 16A AC-3, 100VA

MPNLC1K1610K72
Active

Schneider Electric TeSys K contactor, 3-pole, AC-3 16 A at ≤440 V, 1 NO auxiliary contact, 100 V AC 50/60 Hz coil, screw-clamp terminals.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K1610K72 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC1K1610K72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e

Contacts & Poles

LC1K1610K72 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K1610K72 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94

Approvals

LC1K1610K72 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ

Mechanical

LC1K1610K72 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider TeSys K LC1K1610K72 is a three-pole contactor rated for motor control in AC-3 duty up to 16 A at 440 V. That AC-3 rating means it's built for starting and stopping squirrel-cage induction motors — the standard load type on conveyors, pumps, and fans — where the contacts make and break the motor's locked-rotor current. The 100 V AC coil pulls in at 30 VA inrush and holds at 4.5 VA, with a dropout threshold above 20% of nominal control voltage, so it's compatible with standard 100 V control transformers without additional suppression.

This contactor mounts on either a DIN rail or a plate, with a 45 mm width footprint — that's a single 45 mm module, so it slots into a standard enclosure without eating up rail space. The screw-clamp terminals accept up to 4 mm² solid or 2.5 mm² flexible with ferrules, and the tightening torque range of 0.8 to 1.3 N.m is typical for this class. Depth is 57 mm, height 58 mm — compact enough for shallow back panels.

Electrical durability is 1.3 million cycles at that rating, so it's sized for moderate-duty cycling. The built-in coil suppression (integral suppression device) means you don't need an external RC snubber across the coil for most PLC outputs, but verify the free-wheel diode polarity if the control circuit is DC-switched. Minimum switching capability is 5 mA at 17 V for the signalling circuit, which covers dry-contact feedback to a PLC input.

Frequently asked questions

What compliance documentation does this contactor carry?

It is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. The enclosure is rated IP2X per VDE 0106, and the plastic meets V1 flame retardance per UL 94.

What is the closest alternative in the TeSys K family?

Within the same TeSys K frame, the LC1K1610K7 (with a 24 V AC coil) and the LC1K1610M7 (with a 220 V AC coil) share the same 16 A AC-3 rating, pole configuration, and physical footprint. The only difference is the coil voltage — swap the order code suffix to match your control voltage.

MPN
LC1K1610K72