Skip to main content
Schneider Electric LC2K16017J7 — Contactors

Schneider TeSys K LC2K16017J7 Reversing Contactor, 3P, 16 A

MPNLC2K16017J7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 16 A, 1 NC, 12 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K16017J7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16017J7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K16017J7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16017J7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16017J7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K16017J7 is a TeSys K reversing contactor — a 3-pole, 3 NO power pole unit with a 12 V AC coil and one NC auxiliary contact. It is rated for AC-3 duty at 16 A up to 440 V, which means it handles reversing motor loads (forward-reverse) in control panels. The part ships preassembled with the reversing power busbar, saving panel-build time.

The AC-3 rating of 16 A at <=440 V is the motor-switching current — this contactor can start and stop a reversing 3-phase motor up to that load. The 12 V AC coil means the control circuit must supply 12 VAC; verify your transformer or control voltage matches. IP20 finger-safe protection (VDE 0106) means it is suitable for enclosed panels where accidental contact is prevented by the enclosure door.

Integration notes

Mounts on a DIN rail. Dimensions: 90 mm wide, 58 mm high, 57 mm deep — fits standard panel layouts. The preassembled reversing busbar eliminates external wiring between the two contactor halves for forward and reverse. Operating temperature range is -25 to 50 °C; storage from -50 to 80 °C.

Frequently asked questions

What are the key ratings for this reversing contactor?

It is a 3-pole reversing contactor rated 16 A in AC-3 duty at <=440 V, with a 12 V AC coil and one NC auxiliary contact. The power poles are 3 NO. IP20 protected.

What is the physical size of the LC2K16017J7?

Width 90 mm, height 58 mm, depth 57 mm. DIN-rail mount.

MPN
LC2K16017J7