Skip to main content
Schneider Electric LC2K1601K7 — Contactors

Schneider TeSys K LC2K1601K7 reversing contactor, 3P, AC-3 1

MPNLC2K1601K7
Obsolete

Schneider TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NC, 100 V AC coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K1601K7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K1601K7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-3e
LC2K1601K7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1601K7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1601K7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The 3-pole (3P) power pole arrangement is 3 NO.

Altitude rating to 2000 m without derating covers most installations below that elevation. Mechanical robustness specs — 10 Gn shock on Y/Z axes with contacts closed, 4 Gn vibration closed — mean it holds in on high-vibration machinery like conveyors or compressors, as long as the mounting is rigid.

Mounts on DIN rail (standard 35 mm). The pre-assembled reversing busbar saves panel-builder wiring time, but the fixed width means you need 90 mm of rail per reversing pair. Flame retardance V1 per UL 94 and NF F 16-101/102 means it passes rail and industrial fire-safety requirements. The protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance in humid environments.

Frequently asked questions

What are the key ratings of the LC2K1601K7?

Three-pole reversing contactor, AC-3 motor-switching duty at 16 A up to 440 V, 100 V AC coil, one NC auxiliary contact. IP20 protection, -25 to 50 °C operating ambient, 2000 m altitude rating.

What is the physical size of the LC2K1601K7?

90 mm wide × 58 mm high × 57 mm deep. DIN-rail mount, standard 35 mm rail.

What compliance documentation is available for the LC2K1601K7?

Flame retardance V1 per UL 94, NF F 16-101/102. Protective treatment conforms to IEC 60068 and DIN 50016. IP20 per VDE 0106. No RoHS or REACH statement is in the record.

MPN