Specifications

LC3D80P5 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3D80P5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3
LC3D80P5 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3D80P5 — Environmental
ParameterValue
IP degree of protectionIP2X front face conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor open: 8 Gn for 11 ms Vibrations contactor closed: 3 Gn, 5...300 Hz Shocks contactor closed: 10 Gn for 11 ms
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94

Product details

It carries 3 x 3P (three normally-open power poles) rated at 80 A in AC-3 utilization category, meaning it is sized for switching three-phase induction motors during start-up transition from star to delta configuration. The 230 V AC coil is built into the assembly. This is a pre-wired device — the contactors and timing relay are factory-assembled and wired inside a single enclosure, saving panel wiring time.

The LC3D80P5 is marked Obsolete by Schneider Electric. There is no direct form-fit-function replacement from the current TeSys Deca range that carries the same pre-wired star delta configuration at 80 A with a 230 V AC coil; any substitution requires a panel re-design.

Operates from -40 to 60 °C (derated 60 to 70 °C) and stores from -60 to 80 °C. Fire resistance is 850 °C per IEC 60695-2-1, with flame retardance V1 per UL 94. Protective treatment TH per IEC 60068-2-30 covers tropical humidity exposure. Altitude rating is 3000 m without derating. Mechanical robustness: vibrations 2 Gn (contactor open) and 3 Gn (closed) over 5–300 Hz; shocks 8 Gn for 11 ms (open) and 10 Gn for 11 ms (closed). These ratings matter for machine-tool or conveyor applications where the panel is mounted on the moving equipment.

Frequently asked questions

What replaces the LC3D80P5?

No official successor order code is listed in the available records. Any replacement requires a panel re-design using a current TeSys star delta starter with matching ratings — the 80 A AC-3 and 230 V AC coil are the critical parameters to match.

What is the LC3D80P5's range and product name?

It belongs to the TeSys range, specifically the TeSys D product family, and is classified as a star delta starter.

What compliance documentation exists for this part?

The LC3D80P5 carries fire resistance to 850 °C per IEC 60695-2-1, flame retardance V1 per UL 94, protective treatment TH per IEC 60068-2-30, and IP2X front face protection per IEC 60529. Pollution degree 3 is specified per IEC 60947-1. Full RoHS/REACH documentation would have been provided at original manufacture; for obsolete stock, request compliance certificates from the surplus supplier.

MPN
LC3D80P5