Schneider Electric LC3F115F7 — Contactors

TeSys F LC3F115F7 Star Delta Starter, 115 A AC-3, 110 V AC

MPNLC3F115F7
Obsolete

Schneider Electric TeSys F LC3F115F7, star delta starter, 115 A AC-3, 110 V AC 50/60 Hz coil, 3 x 3 NO power poles, plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC3F115F7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3F115F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3
LC3F115F7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3F115F7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms
Protective treatment / pollution degreeTH
LC3F115F7 — Approvals
ParameterValue
StandardsEN 60947-1 IEC 60947-4-1 IEC 60947-1 EN 60947-4-1 JIS C8201-4-1

Product details

It is rated for AC-3 duty (squirrel-cage motor switching) at 115 A operational current up to 440 V AC, and handles motor power from 52 kW at 220/230 V up to 102 kW at 415/440 V, all at 50/60 Hz. The control circuit runs on 110 V AC 50/60 Hz, with a pick-up range of 0.85 to 1.1 Uc and drop-out between 0.35 and 0.55 Uc at 55 °C. Inrush power is 550 VA at 50 Hz, holding at 45 VA — the coil draw drops significantly once sealed, so the control transformer can be sized for the inrush peak.

Mounts to a plate (not DIN rail) — plan for bolted connection via M6 terminals on the power circuit, accepting ring lugs up to 95 mm² or busbar cross-section 20 x 3 mm. The control circuit uses screw clamp terminals accepting 1 to 4 mm² flexible or solid wire.

Frequently asked questions

What standards does the LC3F115F7 comply with?

It complies with EN 60947-1, IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1.

What is the rated breaking capacity?

Rated breaking capacity is 920 A conforming to IEC 60947-4-1.

What is the mechanical durability?

Mechanical durability is 10 million cycles.