Skip to main content
Schneider Electric LC3F330V7 — Contactors

Schneider Electric TeSys F LC3F330V7 Star Delta Starter, 330

MPNLC3F330V7
Obsolete

Schneider Electric TeSys F LC3F330V7, pre-wired star delta starter, 3 x 3P, 330 A AC-3 at ≤440 V, 400 V AC 50/60 Hz control coil.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC3F330V7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC3F330V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3

Contacts & Poles

LC3F330V7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P

Environmental

LC3F330V7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 6 Gn for 11 ms
Protective treatment / pollution degreeTH

Approvals

LC3F330V7 — Approvals
ParameterValue
StandardsEN 60947-4-1 IEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-1

Mechanical

LC3F330V7 — Mechanical
ParameterValue
Width725 mm
Height110 mm
Depth276 mm

Product details

The Schneider Electric TeSys F LC3F330V7 is a pre-wired star delta starter, purpose-built for motor control in the AC-3 utilisation category — meaning it handles starting and stopping of squirrel-cage motors under load, not just resistive switching. Rated 330 A operational current at ≤440 V AC-3, it delivers 280 kW at 380/400 V AC 50/60 Hz and 315 kW at 440 V AC 50/60 Hz. The 400 V AC 50/60 Hz control coil pulls 650 VA inrush at cos φ 0.9, with a 20-second starting time and closing time of 40 to 65 ms.

The associated fuse rating of 500 A gG or 400 A aM at ≤440 V gives the short-circuit protection boundary; pair it with those fuses to keep the starter within its rated breaking capacity of 2640 A and making capacity of 3300 A per IEC 60947-4-1. The 1000 V rated insulation voltage (IEC 60947-4-1) and 1500 V (VDE 0110 group C) mean it's comfortable on 690 V systems if derated, but the AC-3 current is only specified at ≤440 V — don't assume the same 330 A at higher voltages without checking the manufacturer's derating curve. The 3000 m operating altitude without derating means it's fine for most installations short of high-altitude mines or mountain passes.

This is a plate-mount starter — no DIN rail, so plan for a backplate or mounting panel. Dimensions are 725 mm wide, 276 mm deep, and 110 mm high; it's a substantial unit. Power connections use M10 bolts with bar connections accepting 30 x 5 mm busbars or ring terminals up to 240 mm². Control wiring is via screw clamp terminals accepting 1 to 4 mm² flexible or solid wire.

Frequently asked questions

What are the key ratings I need to check for fit?

The critical ratings are 330 A rated operational current at ≤440 V AC-3, motor power of 280 kW at 380/400 V AC, and a 400 V AC 50/60 Hz control coil. The associated fuse rating is 500 A gG or 400 A aM at ≤440 V.

What compliance standards does this starter meet?

It complies with EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, and JIS C8201-4-1. The rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C.

What is the auxiliary contact configuration?

The star contactor (KM1) has 1 NC + 1 NO, the line contactor (KM2) has 2 NC + 1 NO, and the delta contactor (KM3) has 1 NC + 2 NO. This is a pre-wired assembly, so the interlocking is built in — no separate mechanical interlock required.

MPN