Schneider Electric LC3F400FE7 — Contactors

Schneider Electric LC3F400FE7 TeSys F Star Delta Starter, 40

MPNLC3F400FE7
Obsolete

Schneider Electric TeSys F LC3F400FE7, pre-wired star delta starter, 400 A AC-3 rated operational current, 115 V AC 50/60 Hz control circuit, 315 kW at 400 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC3F400FE7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC3F400FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3

Contacts & Poles

LC3F400FE7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P

Environmental

LC3F400FE7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m with derating factor
Mechanical robustnessShocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 6 Gn for 11 ms Vibrations contactor open: 1.5 Gn, 5...300 Hz
Protective treatment / pollution degreeTH

Approvals

LC3F400FE7 — Approvals
ParameterValue
StandardsIEC 60947-4-1 EN 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1

Mechanical

LC3F400FE7 — Mechanical
ParameterValue
Width725 mm
Height180 mm
Depth276 mm

Product details

Star delta starter for heavy motor loads, 400 A AC-3

Its 400 A rated operational current in AC-3 utilisation category (switching squirrel-cage motors — starting, stopping, and inching) means it handles the high inrush and inductive break of motor starts without welding contacts or exceeding temperature rise limits. The 115 V AC 50/60 Hz control coil pulls 1075 VA inrush at 20 °C, so the control transformer and wiring must be sized for that peak — not the holding dissipation of 14 W.

AC-3 duty at 400 A is the headline number: it governs the motor current the starter can switch under full load, not the resistive heating current. The associated fuse recommendation — 500 A gG or 400 A aM at ≤ 440 V — tells you the upstream protection must coordinate with the starter's 3200 A rated breaking capacity and 4000 A making capacity per IEC 60947-4-1. The 40…65 ms closing and 100…170 ms opening times are fast enough for sequential star-to-delta transition without overlap, provided the control logic respects the 20 s starting time window. Mechanical durability of 10 Mcycles and a maximum operating rate of 2400 cycles per hour at 55 °C mean this starter is rated for frequent cycling — conveyor lines, pump stations, or compressor duty where starts accumulate. The 3000 m altitude derating factor applies above sea level; if the panel sits at elevation, the AC-3 current must be reduced per the manufacturer's curve, though the evidence does not state the exact derating slope.

Frequently asked questions

What are the key ratings of the LC3F400FE7?

It is a 400 A AC-3 star delta starter rated for motors up to 315 kW at 400 V AC, with a 115 V AC control circuit. Breaking capacity is 3200 A, making capacity 4000 A, per IEC 60947-4-1.

What compliance standards does the LC3F400FE7 meet?

It complies with IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1.

What is the depth of the LC3F400FE7?

The depth is 276 mm.

MPN
LC3F400FE7