TeSys F LC3F400M7A64 Star Delta Starter, 400 A AC-3, 220/230

MPNLC3F400M7A64
Obsolete

Schneider Electric TeSys F LC3F400M7A64, pre-wired star delta starter, 400 A rated operational current (AC-3), 220/230 V AC 50/60 Hz control coil, 3 x 3P poles, mechanical interlock, plate mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC3F400M7A64 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC3F400M7A64 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3

Contacts & Poles

LC3F400M7A64 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P

Environmental

LC3F400M7A64 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessShocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 6 Gn for 11 ms Vibrations contactor open: 1.5 Gn, 5...300 Hz
Protective treatment / pollution degreeTH

Approvals

LC3F400M7A64 — Approvals
ParameterValue
StandardsIEC 60947-1 EN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1

Mechanical

LC3F400M7A64 — Mechanical
ParameterValue
Width725 mm
Height180 mm
Depth276 mm

Product details

The Schneider Electric TeSys F LC3F400M7A64 is a pre-wired star delta starter designed for motor control. It integrates three contactors (line, star, delta) with a mechanical interlock in a single assembly, saving panel wiring time and reducing the chance of a mis-wired interlock at startup. Rated for AC-3 utilisation category, it handles 400 A at <= 440 V, which translates to switching squirrel-cage motors up to 375 kW at 440 V. The 400 A AC-3 rating is the key selection number — it governs the motor FLA the starter can handle under starting and jogging duty. The control coil is 220/230 V AC at 50/60 Hz, pulling 1075 VA inrush at cos phi 0.9. Drop-out range is 0.35 to 0.55 Uc, so if your control transformer sags during a line start, this starter drops out predictably — no partial-clutch condition.

Mounts on a plate (not DIN rail), so plan for a backplate or sub-panel in the enclosure. Dimensions are 725 mm wide x 180 mm high x 276 mm deep — this is a large assembly; verify the enclosure depth and swing-clearance for the power circuit bolted connections (M10 bolts, bar cross-section 30 x 5 mm). Power circuit connections accept lugs-ring terminals up to 150 mm² or busbars. Control circuit wiring is screw-clamp terminals accepting 1 to 4 mm² flexible or solid. Tightening torque is 35 N.m on the power circuit and 1.2 N.m on the control circuit — a torque wrench on the power lugs is non-negotiable. IP20 front face protection with shrouds (per IEC 60529 and VDE 0106) means finger-safe from the front once shrouded, but the rear and sides are open — keep clearance from live busbars and follow the manufacturer's minimum separation distances.

Standards compliance covers IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C.

Frequently asked questions

What are the key ratings for the LC3F400M7A64?

Rated operational current is 400 A at <= 440 V in AC-3. Motor power ranges from 185 kW at 220/230 V up to 375 kW at 440 V. Control coil is 220/230 V AC 50/60 Hz. Breaking capacity is 3200 A, making capacity is 4000 A.

What is the auxiliary contact configuration on this starter?

Pre-wired with 1 NC + 1 NO on the star contactor (KM1), 2 NC + 1 NO on the line contactor (KM2), and 1 NC + 2 NO on the delta contactor (KM3). This covers standard star-delta logic without add-on blocks.

What mounting and connection details should I know?

Plate mount only, not DIN rail. Dimensions are 725 x 180 x 276 mm. Power circuit uses M10 bolts and accepts lugs up to 150 mm² or 30 x 5 mm busbars. Control circuit uses screw-clamp terminals, 1 to 4 mm². Tightening torque: 35 N.m power, 1.2 N.m control.

MPN
LC3F400M7A64