Skip to main content
Schneider Electric LC3F400U7 — Contactors

LC3F400U7 TeSys F Star Delta Starter, 400 A AC-3, 240 VAC Co

MPNLC3F400U7
Active

Schneider Electric TeSys F LC3F400U7, pre-wired star delta starter, 3 x 3P, 400 A AC-3 at ≤440 V, 240 V AC 50/60 Hz coil, plate mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC3F400U7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC3F400U7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3

Contacts & Poles

LC3F400U7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P

Environmental

LC3F400U7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Mechanical robustnessShocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open6 Gn for 11 ms Vibrations contactor open1.5 Gn, 5...300 Hz

Approvals

LC3F400U7 — Approvals
ParameterValue
StandardsJIS C8201-4-1 IEC 60947-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1

Mechanical

LC3F400U7 — Mechanical
ParameterValue
Width28.5 in (725 mm)
Height7.09 in (180 mm)
Depth10.9 in (276 mm)

Product details

The LC3F400U7 is a pre-wired TeSys F star delta starter from Schneider Electric. It's built for motor control in AC-3 duty — the category for squirrel-cage motors during starting, running, and plugging. Rated at 400 A operational current at ≤440 V AC, it handles motor loads up to 185 kW on 220/230 V, 315 kW on 380/400 V, 355 kW on 415 V, and 375 kW on 440 V, all at 50/60 Hz. This isn't a bare contactor — it's a pre-assembled star delta assembly with three contactors (star, line, delta), pre-wired for a reduced-voltage start. The contact composition is 3 x 3 NO power poles, with auxiliary contacts: 1 NC and 1 NO on the star contactor, 2 NC and 1 NO on the line contactor, and 1 NC and 2 NO on the delta contactor. That's enough auxiliaries for interlocking and status feedback without adding blocks.

Making capacity is 4000 A, so it handles the inrush when closing into a stalled motor. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C, so it's comfortable in 690 V systems with margin. Control circuit is 240 V AC 50/60 Hz, with a hold range of 0.85 to 1.1 Uc and dropout between 0.35 and 0.55 Uc. Inrush power is 1075 VA at 20 °C — your control transformer needs to handle that peak. That's a rugged unit for frequent starting applications like conveyors or compressors. Heat dissipation is 14 W — negligible for panel thermal calculations.

This is a plate-mount assembly — no DIN rail. Dimensions are substantial: 28.5 inches wide, 10.9 inches deep, 7.09 inches tall. That's a big footprint; plan the backplate layout accordingly. Power connections are via bolted lugs or busbars (30 x 5 mm busbar cross-section recommended), with M10 bolts. Control wiring uses screw clamp terminals accepting 1 to 4 mm² flexible or solid wire. Keep it inside a panel.

Compliance is solid: the starter meets IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. That covers most global panel standards. Associated fuse rating is 500 A gG or 400 A aM at ≤440 V — use that for your short-circuit protection coordination.

Frequently asked questions

What are the key ratings I need to check for fit?

Rated operational current is 400 A at ≤440 V AC in AC-3 duty. Motor power depends on voltage: 185 kW at 230 V, 315 kW at 400 V, 355 kW at 415 V, 375 kW at 440 V. Control coil is 240 V AC 50/60 Hz. Breaking capacity is 3200 A, making capacity 4000 A.

What mounting does this require?

Plate mount only — no DIN rail clip. Dimensions are 28.5 x 10.9 x 7.09 inches. Power connections use M10 bolts or 30 x 5 mm busbars. Control wiring uses screw clamp terminals for 1–4 mm² wire.

What standards does it comply with?

It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC and 1500 V per VDE 0110 group C.

What auxiliary contacts are included?

The star contactor has 1 NC + 1 NO, the line contactor has 2 NC + 1 NO, and the delta contactor has 1 NC + 2 NO. That's 4 NC and 4 NO total — no add-on blocks needed for standard interlocking.

MPN
LC3F400U7