Schneider Electric LP1D40004SW — Contactors

TeSys LP1D40004SW Contactor, 4P, 60 A AC-1, 72 VDC Coil

MPNLP1D40004SW
Obsolete

Schneider Electric TeSys Deca LP1D40004SW, 4-pole contactor, AC-1 440V 60 A, 72 VDC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1D40004SW — Identification
ParameterValue
Product / component typeContactor
ApplicationResistive load
LP1D40004SW — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1 AC-3 AC-3e AC-4
LP1D40004SW — Contacts & Poles
ParameterValue
Pole configuration4P
LP1D40004SW — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529 IP2X conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessShocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
LP1D40004SW — Approvals
ParameterValue
StandardsVDE 0660 IEC 60947-4-1 JEM 1038 BS 5424 NF C 63-110 IEC 60947-1 EN 60947-4-1 EN 60947-1
LP1D40004SW — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth182 mm

Product details

The Schneider Electric LP1D40004SW is a 4-pole contactor from the TeSys Deca range, rated for AC-1 resistive loads at 440 V and 60 A, with a 72 V DC coil.

The AC-1 rating of 60 A at 440 V covers resistive loads like heaters or lighting banks; for motor duty (AC-3) the current rating will be lower — check the specific AC-3 value if driving induction motors. The 72 V DC coil means it needs a 72 VDC supply — not the common 24 VDC or 110 VAC — so verify your control voltage before specifying. It complies with IEC 60947-4-1 and VDE 0660, so it fits panels built to those standards for contactor and motor-starter applications.

Frequently asked questions

What are the key ratings of the LP1D40004SW?

It is a 4-pole contactor rated AC-1 60 A at 440 V with a 72 V DC coil, compliant with IEC 60947-4-1 and VDE 0660.

What compliance documentation is available for the LP1D40004SW?

It meets IEC 60947-4-1, VDE 0660, JEM 1038, BS 5424, NF C 63-110, and EN 60947-1. Fire resistance is 850 °C per IEC 60695-2-1, and flame retardance is V1 per UL 94.