Schneider Electric LP1D65004ED — Contactors

Schneider Electric LP1D65004ED TeSys Deca Contactor, 4P, 80

MPNLP1D65004ED
Obsolete

Schneider Electric TeSys Deca LP1D65004ED, 4-pole contactor, AC-1 440V 80 A, coil 48 V DC, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1D65004ED — Identification
ParameterValue
Product / component typeContactor
ApplicationResistive load
LP1D65004ED — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1 AC-3 AC-3e AC-4
LP1D65004ED — Contacts & Poles
ParameterValue
Pole configuration4P
LP1D65004ED — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529 IP2X conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessShocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
LP1D65004ED — Approvals
ParameterValue
StandardsVDE 0660 NF C 63-110 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1 BS 5424 EN 60947-1 JEM 1038
LP1D65004ED — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth182 mm

Product details

The Schneider Electric LP1D65004ED is a 4-pole contactor from the TeSys Deca range, rated for 80 A in AC-1 duty at 440 V, with a 48 V DC coil. It's built for switching resistive loads, but also covers AC-3 and AC-4 motor duty categories per IEC 60947-4-1 — so it can handle motor starting and inching as well, not just heaters or lighting.

The AC-1 rating of 80 A at 440 V tells you the continuous resistive current it can carry without overheating. For motor loads, you'll need to derate to the AC-3 or AC-4 values — the part's own utilisation category list includes those, but the exact AC-3 current isn't stated here. The 48 V DC coil is a specific control voltage; if your panel runs 24 V DC or 110 V AC, this coil won't pull in.

Mounts on plate or rail, with dimensions 85 mm wide, 127 mm high, 182 mm deep.

Frequently asked questions

What are the key ratings for this contactor?

4 poles, AC-1 rated 80 A at 440 V, coil 48 V DC. It covers utilisation categories AC-1, AC-3, AC-3e, and AC-4. Operating temperature -40 to 60 °C, altitude 3000 m without derating, IP2X protection.

What compliance standards does it meet?

It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, VDE 0660, NF C 63-110, BS 5424, and JEM 1038. Flame retardance is V1 per UL 94, and fire resistance is 850 °C per IEC 60695-2-1. Protective treatment TH (pollution degree 3) per IEC 60068.