Part identity and key ratings
The LP1D65004JD is a 4-pole contactor from the TeSys Deca range, rated for AC-1 resistive loads at 80 A at 440 V, with a 12 V DC coil. It carries utilisation categories AC-1, AC-3, AC-3e, and AC-4, so it handles resistive, motor starting, and inching/jogging duty within its rated current envelope. The 12 V DC coil is a specific control voltage — verify your control circuit matches before committing the BOM line. The contactor is rated for operation at altitudes up to 3000 m without derating, and the permissible ambient air temperature spans -40 to 60 °C (with derating up to 70 °C).
Standards and approvals
This contactor is certified to IEC 60947-4-1, EN 60947-4-1, VDE 0660, BS 5424, NF C 63-110, and JEM 1038 — the core standards for contactors and motor-starters. It carries IP2X finger protection per IEC 60529 and VDE 0106, and the housing is flame retardant to UL 94 V1 with fire resistance at 850 °C per IEC 60695-2-1. Protective treatment TH (pollution degree 3) per IEC 60068 means it's suitable for industrial environments with conductive pollution.
Mounting and integration
Mounts on plate or DIN rail (mounting support listed as plate/rail). The 4-pole footprint is 85 mm wide, 127 mm tall, and 182 mm deep — standard for a TeSys Deca frame this size. Non-overlap time between NC and NO contacts is 1.5 ms on both energisation and de-energisation, which matters for interlocking circuits where contact overlap could cause a short.