The LP1D65004JD is a 4-pole contactor from the TeSys Deca range, rated for AC-1 resistive loads at 80 A at 440 V, with a 12 V DC coil. It carries utilisation categories AC-1, AC-3, AC-3e, and AC-4, so it handles resistive, motor starting, and inching/jogging duty within its rated current envelope. The 12 V DC coil is a specific control voltage — verify your control circuit matches before committing the BOM line.
This contactor is certified to IEC 60947-4-1, EN 60947-4-1, VDE 0660, BS 5424, NF C 63-110, and JEM 1038 — the core standards for contactors and motor-starters. It carries IP2X finger protection per IEC 60529 and VDE 0106, and the housing is flame retardant to UL 94 V1 with fire resistance at 850 °C per IEC 60695-2-1.
Mounts on plate or DIN rail (mounting support listed as plate/rail). The 4-pole footprint is 85 mm wide, 127 mm tall, and 182 mm deep — standard for a TeSys Deca frame this size.