What it is and what it does
The Schneider Electric LP1D65004JW is a 4-pole contactor from the TeSys Deca range, rated for AC-1 resistive loads at 80 A and 440 V, with a 12 V DC coil. It is designed for switching resistive loads in control panels and industrial machinery, certified to EN 60947-4-1 and IEC 60947-1.
Lifecycle and sourcing reality
This part is obsolete per the manufacturer. No direct successor is listed in the evidence. Sourcing runs through surplus and broker channels; we can quote to order against an RFQ.
Key ratings and what they mean for fit
Rated for AC-1 (resistive), AC-3 (squirrel-cage motor starting), AC-3e (enhanced motor), and AC-4 (inching/plugging) duty categories. The AC-1 80 A rating at 440 V covers resistive heater or lighting loads; for motor duty, the AC-3 current will be lower — verify against your motor full-load amps. The 12 V DC coil is common in low-voltage control circuits, often fed from a PLC or relay output. Mounts on a rail or plate, with dimensions 85 mm wide × 127 mm high × 182 mm deep — check panel clearance for the depth, especially in shallow enclosures. IP2X finger protection means it is safe for open-panel mounting but not for washdown environments. Operates from -40 °C to 60 °C without derating, with derating possible up to 70 °C. Storage range extends from -60 °C to 80 °C. No derating needed up to 3000 m altitude — suitable for most industrial sites.
Compliance and approvals
Certified to EN 60947-4-1, IEC 60947-1, NF C 63-110, JEM 1038, VDE 0660, and BS 5424. Fire resistance rated at 850 °C per IEC 60695-2-1, flame retardance V1 per UL 94. Protective treatment TH (pollution degree 3) per IEC 60068.