Skip to main content
Schneider Electric LP1D65004MD — Contactors

TeSys LP1D65004MD Contactor, 4P, AC-1 80A, 220 VDC Coil

MPNLP1D65004MD
Active

Schneider Electric TeSys Deca LP1D, 4-pole contactor, AC-1 80A at 440V, coil 220 VDC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1D65004MD — Identification
ParameterValue
Product / component typeContactor
ApplicationResistive load
LP1D65004MD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1 AC-3 AC-3e AC-4
LP1D65004MD — Contacts & Poles
ParameterValue
Pole configuration4P
LP1D65004MD — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529 IP2X conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessShocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
LP1D65004MD — Approvals
ParameterValue
StandardsVDE 0660 EN 60947-1 IEC 60947-1 BS 5424 IEC 60947-4-1 NF C 63-110 JEM 1038 EN 60947-4-1
LP1D65004MD — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth182 mm

Product details

The Schneider Electric LP1D65004MD is a 4-pole contactor from the TeSys Deca range, rated AC-1 80 A at 440 V for resistive loads, with a 220 V DC coil. For motor duty, it also carries AC-3 and AC-4 utilisation categories, so it handles squirrel-cage motors up to its rated switching capacity without welding contacts on start-up. Non-overlap time between NC and NO contacts is 1.5 ms on both energisation and de-energisation — that matters if you're interlocking two contactors for reversing or star-delta transitions; the delay prevents a momentary short across the poles.

Where it goes and what it connects to

Mounts on a rail or plate — the 85 mm width and 127 mm height fit a standard TeSys Deca footprint, so it swaps into an existing panel layout without re-drilling. IP2X finger protection means the live terminals are shielded from accidental contact inside an enclosure, which is the minimum for a panel-mounted contactor behind a locked door.

Compliant with IEC 60947-4-1 (the main contactor standard), EN 60947-1, VDE 0660, BS 5424, NF C 63-110, and JEM 1038.

Frequently asked questions

What are the key ratings for this contactor?

4 poles, AC-1 80 A at 440 V for resistive loads, 220 V DC coil. It also covers AC-3 and AC-4 motor duty categories. Non-overlap time is 1.5 ms between NC and NO contacts.

What compliance documentation does this part carry?

It complies with IEC 60947-4-1, EN 60947-1, VDE 0660, BS 5424, NF C 63-110, and JEM 1038. Fire resistance is 850 °C per IEC 60695-2-1, flame retardance is V-1 per UL 94, and protective treatment is TH (pollution degree 3) per IEC 60068.

MPN