Skip to main content
Schneider Electric LP1D65004RD — Contactors

Schneider LP1D65004RD TeSys D Contactor, 80A AC-1, 4P, 440V

MPNLP1D65004RD
Active

Schneider Electric TeSys D, contactor, 80 A, 4 poles, AC-1 utilisation category, 440 V rated operational voltage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1D65004RD — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control
LP1D65004RD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)440 V
Utilisation categoryAC-1
LP1D65004RD — Contacts & Poles
ParameterValue
Pole configuration4P
LP1D65004RD — Environmental
ParameterValue
Operating altitude0...9842.52 ft (0...3000 m)
LP1D65004RD — Mechanical
ParameterValue
Width3.3 in (85 mm)
Height5 in (127 mm)
Depth7.2 in (182 mm)
LP1D65004RD — Other specifications
ParameterValue
Protective coverWithout
Device short nameLP1D
Control circuit voltage limits0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.1 Uc (131...158 °F (55...70 °C)):operational DC
[Ie] rated operational current80 A
Permissible ambient air temperature around the device-76...176 °F (-60...80 °C) storage -40...140 °F (-40...60 °C) operation 140...158 °F (60...70 °C) with derating

Product details

The LP1D65004RD: The 80 A rating is under AC-1, which covers resistive loads — heaters, lighting banks, non-inductive circuits. For motor duty (AC-3), the rated current will be lower; the datasheet's AC-3 figure governs the real motor branch circuit. The 440 V operational voltage matches standard three-phase distribution in many industrial and commercial panels. Four poles give you the ability to switch all three phases plus a neutral, or use the fourth pole for an auxiliary load. The open-frame design (no protective cover) means it's intended for enclosed panel mounting, not standalone exposed installation. Physical footprint: 7.2 in (182 mm) deep, 3.3 in (85 mm) wide, 5 in (127 mm) tall. That's a standard TeSys D envelope — fits the same DIN-rail or screw-mount pattern as other TeSys D contactors, so a panel layout swap from a different rating in the same family doesn't require re-drilling.

The 4-pole width is the same as a standard 3-pole plus one auxiliary block, so panel fill factor is predictable. Operating ambient range from -40 to 140 °F (-40 to 60 °C), with derating above 140 °F — fine for most ventilated enclosures but worth noting if the panel sits near a heat source.

Frequently asked questions

What is the physical size of the LP1D65004RD?

Depth is 7.2 in (182 mm), width 3.3 in (85 mm), height 5 in (127 mm). Standard TeSys D footprint.

What is the TeSys range?

TeSys is Schneider Electric's family of motor control and protection components. The LP1D65004RD is a TeSys D contactor, the compact general-purpose series within that range.

MPN