Skip to main content
Schneider Electric LP1K06016BD3 — Contactors

Schneider TeSys K LP1K06016BD3 Contactor, 6A, 24V DC Coil, O

MPNLP1K06016BD3
Obsolete

Schneider Electric TeSys K series, LP1K06016BD3, 3-pole contactor, 6 A rated operational current, 24 V DC coil with built-in diode suppressor, 1 NC auxiliary contact, obsolete lifecycle.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1K06016BD3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LP1K06016BD3 — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-4
LP1K06016BD3 — Contacts & Poles
ParameterValue
Pole configuration3P
LP1K06016BD3 — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K06016BD3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LP1K06016BD3 — Other specifications
ParameterValue
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Range of productTeSys K
Device short nameLP1K
Inrush power in3 W (at 20 °C)
Compatibility codeLP1K
Pole contact composition3 NO
Hold-in power consumption in3 W at 20 °C
[Ie] rated operational current6 A at 10 MOhm for signalling circuit

Product details

The LP1K06016BD3 is a 3-pole contactor from the TeSys K range, rated for AC-3 and AC-4 utilisation categories up to 440 V. Its 6 A rated operational current covers small motor switching and signalling circuits. The 24 V DC coil includes a built-in bidirectional peak limiting diode suppressor, which simplifies panel wiring by eliminating the need for an external flyback diode across the coil. Flame retardance is V1 per UL 94, also meeting NF F 16-101 and NF F 16-102 Requirement 2 — relevant for rail and transit applications where fire-smoke-toxicity compliance is specified.

Integration into a panel

The 3 NO main poles and 1 NC auxiliary contact are pre-configured; no auxiliary block to add for basic signalling. Coil hold-in power is 3 W at 20 °C, with the same 3 W inrush. The built-in diode suppressor handles back-EMF, so no additional snubber is needed on the DC coil circuit — just confirm polarity before energising.

Frequently asked questions

What is the closest alternative to LP1K06016BD3?

No official successor order code is listed. A parametric replacement would need the same 3-pole, 6 A AC-3 rating, 24 V DC coil, and 1 NC auxiliary. Verify pinout and mounting compatibility against your existing panel layout before ordering a substitute.

What are the key specifications of LP1K06016BD3?

3-pole contactor, 6 A rated operational current in AC-3/AC-4 categories up to 440 V, 24 V DC coil with built-in diode suppressor, 1 NC auxiliary contact. Dimensions: 45 x 58 x 57 mm. Flame retardance V1 per UL 94.

What compliance documentation is available for this part?

The part carries UL 94 V-1 flame retardance and meets NF F 16-101 and NF F 16-102 Requirement 2 for rail applications. Standard Schneider documentation for TeSys K series applies — consult the product certificate for full RoHS/REACH status.

MPN
LP1K06016BD3