Skip to main content
Schneider Electric LP1K06105ED — Contactors

TeSys K LP1K06105ED Contactor, 3P, 6A, 48 VDC Coil

MPNLP1K06105ED
Active

TeSys K, Contactor, 3P, AC-3 ≤440V 6A, 48 VDC coil, 1 NO aux, 3 NO main poles, depth 57 mm, width 45 mm, height 58 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP1K06105ED — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
LP1K06105ED — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-3
LP1K06105ED — Contacts & Poles
ParameterValue
Pole configuration3P
LP1K06105ED — Environmental
ParameterValue
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K06105ED — Mechanical
ParameterValue
Width1.8 in (45 mm)
Height2.3 in (58 mm)
Depth2.2 in (57 mm)

Product details

The TeSys K LP1K06105ED is a 3-pole contactor with a 48 VDC coil, rated for 6 A in AC-3 duty up to 440 V. That AC-3 rating means it's built for starting and stopping squirrel-cage motors — the kind you see on pumps, fans, and conveyors. The 3 NO main poles and one NO auxiliary contact give you the basic switching and feedback for a motor starter or a small load group.

The 3 W hold-in power at 20 °C is low enough that a small 48 VDC supply can handle it without a separate power bus.

Use it in a control panel for switching motor loads or resistive loads up to its rated current. The AC-4 category also covers inching and plugging duty — so if your application does frequent jogging or reversing, this contactor can handle the higher switching stress that comes with those cycles.

Frequently asked questions

What are the key ratings for the LP1K06105ED?

It's a 3-pole contactor rated 6 A at 440 V in AC-3 (motor starting) and AC-4 (inching/plugging) duty. The coil is 48 VDC, hold-in power is 3 W at 20 °C. It has 3 NO main poles and 1 NO auxiliary contact.

What compliance documentation does this brand provide for the LP1K06105ED?

The part carries a V1 flame retardance rating per UL 94 and also meets NF F 16-101 and NF F 16-102 requirements for fire behavior in rail applications. Standard TeSys K documentation includes UL, CSA, and CE declarations; specific certificates should be requested with the RFQ.

MPN