Skip to main content
Schneider Electric LP1K09004BDTQ — Contactors

TeSys LP1K09004BDTQ Contactor, 4P AC-1 20A, 24 VDC Coil

MPNLP1K09004BDTQ
Active

Schneider Electric TeSys K series, LP1K09004BDTQ, 4-pole contactor, AC-1 440 V 20 A, 24 V DC coil with built-in bidirectional peak limiting diode suppression.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1K09004BDTQ — Identification
ParameterValue
Product / component typeContactor
LP1K09004BDTQ — Ratings & Performance
ParameterValue
Utilisation categoryAC-1
LP1K09004BDTQ — Contacts & Poles
ParameterValue
Pole configuration4P
LP1K09004BDTQ — Environmental
ParameterValue
Flame retardanceClass C2 conforming to NF F 16-101 Class C2 conforming to NF F 16-102 V1 conforming to UL 94
LP1K09004BDTQ — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm
LP1K09004BDTQ — Other specifications
ParameterValue
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Range of productTeSys K
Device short nameLP1K
Inrush power in3 W (at 20 °C)
Compatibility codeLP1K
Control circuit typeDC
Pole contact composition4 NO
Rated operational power in120 W at 24 V DC-13 - electrical durability: 1000000 cycles - for control circuit 15 W at 24 V DC-13 - electrical durability: 10000000 cycles - for control circuit 55 W at 24 V DC-13 - electrical durability: 3000000 cycles - for control circuit
Hold-in power consumption in3 W at 20 °C
[Ie] rated operational current20 A (at 10 MOhm for control circuit

Product details

The LP1K09004BDTQ is a TeSys K 4-pole contactor from Schneider Electric, rated 20 A in AC-1 utilisation category at 440 V. AC-1 covers resistive or lightly inductive loads — heaters, lighting banks, transformer primaries — where the switching arc is easier on the contacts than motor starting.

DC-13 solenoid load endurance

For DC-13 duty — switching solenoids, brakes, or clutches on a 24 V DC line — the contactor is rated 120 W at 1 million cycles, 55 W at 3 million cycles, and 15 W at 10 million cycles. That matters when you're cycling a valve or brake frequently: pick the power level that matches your expected service life, because the arc on DC inductive loads wears the contacts faster than AC resistive switching.

Frequently asked questions

What are the key dimensions of this contactor?

Width 45 mm, height 58 mm, depth 57 mm. That 45 mm width is the critical panel-space dimension for DIN-rail layout.

What compliance certifications does this part carry?

The housing is rated V1 per UL 94 for flammability, and Class C2 per NF F 16-101 and NF F 16-102 for railway rolling-stock fire behaviour. The coil includes a built-in bidirectional peak limiting diode suppressor.

MPN