Schneider Electric LP1K09004FD3 — Contactors

TeSys K LP1K09004FD3 Contactor, 4P 20A 110VDC Coil

MPNLP1K09004FD3
Obsolete

Schneider Electric TeSys K contactor, LP1K09004FD3, 4P (4 NO), AC-1 utilisation category, 20 A rated operational current, 110 V DC coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1K09004FD3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LP1K09004FD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP1K09004FD3 — Contacts & Poles
ParameterValue
Pole configuration4P
LP1K09004FD3 — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K09004FD3 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LP1K09004FD3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LP1K09004FD3 is a 4-pole (4 NO) contactor from the TeSys K range, rated 20 A in AC-1 utilisation category at 690 V AC. That 20 A figure is the conventional free-air thermal current (Ith) at 50 °C — the continuous current the power circuit can carry in open air. For a resistive load application, the rated operational current (Ie) matches that 20 A at 690 V, derating to 16 A above 70 °C. The 110 V DC coil pulls 3 W inrush at 20 °C and holds at the same 3 W, with a built-in bidirectional peak limiting diode suppressor for back-EMF control. Breaking capacity is 110 A across the common 220–440 V range, dropping to 80 A at 500 V and 70 A at 660–690 V. That means it clears faults reliably up to those levels without welding contacts — important for coordination with upstream protection. The associated fuse recommendation is 25 A gG or aM for the power circuit. For safety-related circuits, the B10d value is 1,369,863 cycles under nominal load per EN/ISO 13849-1, and 20 million cycles under mechanical load only.

Screw-clamp terminals accept a Philips No 2 or flat 6 mm screwdriver at 1.3 N·m torque. Operating temperature range is -25 to 50 °C, storage -50 to 80 °C, with no derating needed up to 2000 m altitude.

Compliance is broad: certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. The insulation voltage is 690 V per IEC, 600 V per UL/CSA. Impulse withstand is 8 kV, overvoltage category III.

Frequently asked questions

What is the closest alternative to the LP1K09004FD3 in the same family?

Within the TeSys K range, the closest functional sibling would be a 4-pole contactor with the same 20 A AC-1 rating but a different coil voltage. The LP1K09004FD3 is specific to 110 V DC coil; if your control voltage differs, the same mechanical platform is available with other coil options. No pin-compatible drop-in with a different coil exists — the coil voltage is the only variant parameter.

What compliance documentation is available for this contactor?

The LP1K09004FD3 carries certifications to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. Flame retardance is V1 per UL 94 and meets NF F 16-101/102 requirements. The manufacturer provides a declaration of conformity covering these standards.

MPN