Skip to main content
Schneider Electric LP1K090085JD — Contactors

Schneider Electric LP1K090085JD TeSys K Contactor, 20A AC-1,

MPNLP1K090085JD
Active

Schneider Electric TeSys K contactor, LP1K090085JD, 4P (2 NO + 2 NC), AC-1, ≤440 V, 20 A, 12 V DC coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP1K090085JD — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LP1K090085JD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP1K090085JD — Contacts & Poles
ParameterValue
Pole configuration4P
LP1K090085JD — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K090085JD — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LP1K090085JD — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LP1K090085JD is a TeSys K contactor — a 4-pole (2 NO + 2 NC) device rated for AC-1 resistive loads up to 20 A at 690 V AC 50/60 Hz, with a 12 V DC coil. Coil pull-in is 30…40 ms; drop-out is 10 ms on NO opening and 15 ms on NC closing. The control circuit operates from 0.8 to 1.15 Uc and drops out between 0.1 and 0.75 Uc below 50 °C. Hold-in power consumption is 3 W at 20 °C.

The contactor mounts on printed circuit boards — not a standard DIN-rail footprint — so plan for PCB integration rather than panel rail. Rated breaking capacity is 110 A at 415 V and 440 V, derating to 80 A at 500 V and 70 A at 660…690 V. The associated fuse is 25 A gG or aM for the power circuit. Mechanical durability is 10 million cycles; maximum operating rate is 3600 cycles per hour.

Compliant with EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 600 V per UL 508 and CSA C22.2 No 14, and 690 V per IEC 60947-4-1. Impulse withstand voltage (Uimp) is 8 kV. Overvoltage category III. Flame retardance is V1 per UL 94 and meets NF F 16-101/102 Requirement 2.

Frequently asked questions

What are the key ratings for this contactor?

AC-1 rated operational current 20 A at 690 V, 4 poles (2 NO + 2 NC), 12 V DC coil. Breaking capacity 110 A at 415/440 V. Mechanical durability 10 million cycles.

What compliance documentation does this part carry?

It is certified to IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. Flame retardance V1 per UL 94.

What is the physical size of LP1K090085JD?

45 mm wide, 58 mm high, 57 mm deep. Mounts on printed circuit boards.

MPN