Skip to main content
Schneider Electric LP1K09008JD3 — Contactors

TeSys K LP1K09008JD3 Contactor, 4P 20A AC-1, 12V DC Coil

MPNLP1K09008JD3
Active

Schneider Electric TeSys K contactor, 4P (2 NO + 2 NC), AC-1, ≤440 V, 20 A, 12 V DC coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP1K09008JD3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LP1K09008JD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP1K09008JD3 — Contacts & Poles
ParameterValue
Pole configuration4P
LP1K09008JD3 — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K09008JD3 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LP1K09008JD3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LP1K09008JD3 is a TeSys K contactor from Schneider Electric, a 4-pole (2 NO + 2 NC) device rated for 20 A in AC-1 utilisation category at ≤ 440 V, with a 12 V DC coil. It is designed for switching resistive loads in control panels and industrial machinery. The 20 A conventional free-air thermal current (Ith) at 50 °C and the 20 A rated operational current (Ie) at 690 V AC in AC-1 duty mean this contactor handles resistive heating loads like heater banks or lighting circuits up to that current. The AC-1 rating is the key selection parameter — it governs the continuous current the contacts can carry without derating for inductive motor inrush. Mounts on a plate or DIN rail, with a 45 mm width, 58 mm height, and 57 mm depth — fits standard 45 mm modular enclosure spacing. Screw-clamp terminals accept a Philips No 2 or flat Ø 6 mm screwdriver, torqued to 1.3 N·m.

The 12 V DC coil includes a built-in bidirectional peak limiting diode suppressor, so no external flyback diode is needed across the coil — saves a component and a wiring step. Coil energisation to NO closing takes 30…40 ms; de-energisation to NO opening takes 10 ms. The control circuit operates between 0.8 and 1.15 Uc and drops out between 0.1 and 0.75 Uc below 50 °C. Inrush power is 3 W at 20 °C; hold-in power consumption is also 3 W at 20 °C — the coil draws steady power once sealed, no spike after the initial pull-in.

Breaking capacity and protection

Rated breaking capacity reaches 110 A at 415 V and 440 V, 80 A at 500 V, and 70 A at 660…690 V, all conforming to IEC 60947. The rated making capacity is 110 A AC for the power circuit. For short-circuit protection, the associated fuse rating is 25 A gG or 25 A aM for the power circuit. Rated insulation voltage (Ui) is 690 V per IEC 60947-4-1, 600 V per UL 508 and CSA C22.2 No 14. Impulse withstand voltage (Uimp) is 8 kV, overvoltage category III — suitable for fixed-installation distribution panels where transient overvoltages from the mains are expected.

Certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Flame retardance meets V1 per UL 94 and Requirement 2 per NF F 16-101 and NF F 16-102. Safety reliability level: B10d = 1,369,863 cycles with nominal load and 20,000,000 cycles with mechanical load, per EN/ISO 13849-1.

Environmental limits

Operates at -25…50 °C ambient, stores at -50…80 °C. Maximum operating rate is 3600 cycles per hour. Mechanical durability is 10 million cycles.

Frequently asked questions

What are the key ratings for this contactor?

The LP1K09008JD3 is a 4-pole (2 NO + 2 NC) contactor rated 20 A in AC-1 utilisation category at ≤ 440 V, with a 12 V DC coil. The conventional free-air thermal current (Ith) is 20 A at 50 °C. Breaking capacity reaches 110 A at 415/440 V.

What compliance documentation does this part carry?

It is certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Flame retardance is V1 per UL 94. Safety reliability is documented per EN/ISO 13849-1 with B10d values of 1,369,863 cycles (nominal load) and 20,000,000 cycles (mechanical load).

What are the physical dimensions of the LP1K09008JD3?

Width 45 mm, height 58 mm, depth 57 mm. It mounts on a plate or DIN rail.

MPN
LP1K09008JD3