Skip to main content
Schneider Electric LP1K09008LD — Contactors

Schneider TeSys K LP1K09008LD Contactor, 4P 2NO+2NC, 20A AC-

MPNLP1K09008LD
Active

Schneider Electric TeSys K contactor, 4P (2 NO + 2 NC), AC-1 ≤440V, 20A, 200V DC coil, LP1K09008LD.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LP1K09008LD — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LP1K09008LD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP1K09008LD — Contacts & Poles
ParameterValue
Pole configuration4P
LP1K09008LD — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K09008LD — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LP1K09008LD — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric TeSys K LP1K09008LD is a 4-pole contactor with a 2 NO + 2 NC pole configuration, rated for 20 A in AC-1 utilisation category (resistive loads) at up to 690 V AC 50/60 Hz on the power circuit. The coil is 200 V DC. Rated breaking capacity reaches 110 A at 415 V, 440 V, 220…230 V, and 380…400 V per IEC 60947; 80 A at 500 V; and 70 A at 660…690 V. The conventional free-air thermal current (Ith) is 20 A at 50 °C for the power circuit.

The 20 A AC-1 rating means this contactor is sized for resistive loads — heaters, lighting banks, or non-inductive circuits — not for motor starting. AC-1 is the least demanding switching duty; if your BOM calls for motor loads (AC-3), this part is underspecified. The 2 NO + 2 NC pole arrangement gives flexibility for interlocking or auxiliary switching within the same package. Rated insulation voltage (Ui) is 690 V per IEC 60947-4-1 and 600 V per UL 508 / CSA C22.2 No 14, with an impulse withstand voltage (Uimp) of 8 kV. Overvoltage category III means it's suitable for fixed-installation distribution panels, not for surge-prone outdoor feeders.

Safety reliability data is published: B10d = 1,369,863 cycles for the contactor with nominal load per EN/ISO 13849-1, and B10d = 20,000,000 cycles with mechanical load only. This supports SIL/PL assessments for safety circuits using the NC mirror contacts.

Mounts on rail or plate. Screw-clamp terminals accept a Philips No 2 or flat 6 mm screwdriver at 1.3 N·m torque. Maximum operating rate is 3600 cycles per hour.

Frequently asked questions

What is the closest pin-compatible alternative in the TeSys family?

Within the TeSys K range, the LP1K series shares the same footprint and pole configuration. The key differentiator is the coil voltage — this unit uses a 200 V DC coil. A peer with a different coil voltage (e.g., 24 V DC or 230 V AC) would require a different order code but the same mechanical mounting and terminal layout.

What is the depth of LP1K09008LD?

The depth is 57 mm.

What is the product range for LP1K09008LD?

It belongs to the TeSys K range of contactors from Schneider Electric.

What compliance documentation is available for LP1K09008LD?

The contactor is certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Flame retardance is V1 per UL 94. Safety reliability data (B10d) per EN/ISO 13849-1 is published.

MPN
LP1K09008LD