That's not a motor rating — for motor switching you'd need the AC-3 duty class, which this part doesn't list. The 690 V insulation voltage (Ui) and 8 kV impulse withstand (Uimp) put it solidly in IEC 60947-4-1 territory for industrial control panels.
Deployment context
The 58 mm height and 45 mm width leave room for finger-duct and wiring around it. Coil energization takes 30–40 ms to close the NO contacts, 10 ms to open them on de-energization — fast enough for most sequencing but not for high-speed cycling; the maximum operating rate is 3600 cycles per hour. The 3 W hold-in power means the coil driver doesn't need oversized DC supplies.
Screw-clamp terminals accept up to a certain wire gauge; tighten to 1.3 N·m using a #2 Philips or 6 mm flat-blade screwdriver. The power circuit impedance is 3 mΩ at 20 A, 50 Hz — low enough to keep voltage drop negligible in a control panel. Operating temperature range is -25 to 50 °C, storage from -50 to 80 °C, and it works at altitudes up to 2000 m without derating.