Skip to main content
Schneider Electric LP1K09103ED — Contactors

Schneider LP1K09103ED TeSys K Contactor, 9A AC-3, 48V DC

MPNLP1K09103ED
Obsolete

Schneider Electric TeSys K contactor, LP1K09103ED, 3P, AC-3 ≤440V 9A, 1 NO aux, 48V DC coil, obsolete.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LP1K09103ED — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys

Ratings & Performance

LP1K09103ED — Ratings & Performance
ParameterValue
Utilisation categoryAC-4 AC-1 AC-3

Contacts & Poles

LP1K09103ED — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LP1K09103ED — Environmental
ParameterValue
Flame retardanceV1 UL 94 Requirement 2 NF F 16-101 Requirement 2 NF F 16-102

Mechanical

LP1K09103ED — Mechanical
ParameterValue
Width1.8 in (45 mm)
Height2.3 in (58 mm)
Depth2.2 in (57 mm)

Other specifications

LP1K09103ED — Other specifications
ParameterValue
Range of productTeSys K
Device short nameLP1K
Inrush power in3 W 68 °F (20 °C))
Compatibility codeLP1K
Pole contact composition3 NO
Hold-in power consumption in3 W 68 °F (20 °C)
[Ie] rated operational current20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit

Product details

The Schneider Electric LP1K09103ED is a TeSys K series contactor with 3 normally-open power poles, rated for AC-3 switching duty at 9 A up to 440 V, plus one NO auxiliary contact. The coil is 48 V DC, drawing 3 W holding power at 20 °C. It also carries an AC-1 resistive rating of 20 A and an AC-4 category for high-inrush loads like plugging or inching. Flame retardance meets UL 94 V1 and NF F 16-101/102 requirements, which matters for rail and transit panel compliance. The compact footprint — 45 mm wide, 58 mm tall, 57 mm deep — fits standard DIN-rail enclosures where panel space is tight.

This part is marked obsolete by the manufacturer. If you're qualifying a replacement, the TeSys K family shares the same panel footprint and coil voltage options, but pin compatibility and aux contact arrangement must be verified per your circuit.

The AC-3 rating of 9 A is the figure that governs motor switching — it's the current the contactor can make and break across a standard squirrel-cage motor starting profile. The AC-1 rating of 20 A applies to resistive loads only; don't substitute it for the motor duty figure. The 48 V DC coil is common in control circuits fed from a 48 V battery-backed bus or a DC power supply; verify your control voltage matches the coil tolerance band (typically 0.7–1.2× nominal for DC-operated TeSys K contactors).

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current is 9 A in AC-3 (motor switching) up to 440 V, and 20 A in AC-1 (resistive). Coil is 48 V DC with 3 W holding power. Three NO power poles plus one NO auxiliary contact.

What compliance documentation is available for this part?

The contactor carries UL 94 V1 flame retardance rating and meets NF F 16-101/102 requirements for rail rolling stock. Standard Schneider Electric declarations for RoHS and REACH are available through the brand's documentation portal.

MPN
LP1K09103ED